3. THERMOSTAT CAREL IR33W- SET PARAMETERS FRIDGE CABINETS
1
Carel ir33
1. Compressor ON
2. Key "Prg/ mute"
3. Key "UP"
TO SET THE IR33 AS A TEMPERATURE DISPLAY ONLY (Thermometer)
ENGINEER ONLY SETTINGS, PLEASE READ AND UNDERSTAND
Factory Reset (only required if parameters in table below have been unknowingly changed)
1. To set default parameter values switch off instrument.
2. Switch back on, hold "Prg/ mute " key (2) until the message "Std " is shown on the display.
How to change the SET PARAMETERS
1. To access the set parameter codes- press and hold "Prg / mute" (2) & "Set" (4) keys together for 5
seconds. The display will show "00".
2. Press the "UP" arrow key (3) until you reach value 22 and then press "Set" (4) to confirm (you will
now be in the configuration parameters)
3. Use the "UP' and "Down" arrow keys (3) (5) to change between parameter codes (see table on next
page for codes)
.
4. Press "Set" (4) to view or change the values within parameter code.
5. Use the "UP' and "Down" arrow keys (3) 5) to increase or decrease value of parameter code.
6. Once you have required value press "Set" (4) to save.
7. Repeat steps 3 to 6 to set other parameters. The icons shown on the display correspond to the
category of parameter (see table below).
8. To permanently save the values and exit, press "Prg/mute" and hold for more than 5 seconds.
OPERATING INSTRUCTIONS CAREL IR33 (G60875, G60890)
AS A THERMOMETER ONLY
2
3
4
5
4. Key "Set"
5. Key "DOWN"
2
3
4
5
Control Keys
1
Display
:
FULLY BEFORE PROCEEDING