EMC Immunity Type Tests per IEEE 1613
Note
The RUGGEDCOM RS910L meets Class 2 requirements for an all-fiber configuration
and Class 1 requirements for copper ports. Class 1 allows for temporary communica-
tion loss, while Class 2 requires error-free and interrupted communications.
Fast Transient
Dielectric Strength
Environmental Type Tests
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEC 60255-21-1
IEC 60255-21-2
RUGGEDCOM RS910L
Installation Manual, 02/2020, C79000-G8976-1030-06
Description
ESD
Radiated RFI
Oscillatory
HV Impulse
Test
Cold Temperature
Dry Heat
Humidity (Damp
Heat, Cyclic)
6.2 EMC and Environmental Type Tests
Enclosure Contact
Enclosure Air
Enclosure Ports
Signal Ports
DC Power Ports
AC Power Ports
Earth Ground Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Signal Ports
DC Power Ports
AC Power Ports
Description
Test Ad
Test Bd
Test Db
Vibration
Shock
Certification
Test Levels
± 8 kV
± 15 kV
35 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
± 4 kV
2.5 kV Common Mode @ 1 MHz
2.5 kV Common and Dif-
ferential Mode @ 1 MHz
2.5 kV Common and Dif-
ferential Mode @ 1 MHz
5 kV (Failsafe Relay)
5 kV
5 kV
2 kV (Failsafe Relay)
2 kV
2 kV
Test Levels
Severity Levels
-40 °C (-40
°F), 16 Hours
85 °C (185
°F), 16 Hours
95% (Non-Con-
densing), 55 °C
(131 °F), 6 Cycles
2 g @ 10 to 150 Hz
30 g @ 11 ms
 
 
 
Class 2
Class 2
39