Preferred Method - Harman Stove Company P61A-2 Owner's Manual

Hide thumbs Also See for P61A-2:
Table of Contents

Advertisement

#I Preferred method
This method provides excellent venting for normal
operation and allows the stove to be installed closest to
the wall. Two inches h m the wall is safe; however, four
inches allows better access to remove the rear panel.
The vertical portion of the vent should be three to five
feet high. This vertical section will provide natural draft
in the event of apower failure.
Fig. 8
1
3 ft.
1
to combustibles
#2 Preferred method
This method also provides excellent venting for
normal operation but requires the stove to be installed
farther from the wall. The vertical portion of the vent
should be three to five feet high and at least three inches
fiom a combustible wall. T h ~ s vertical section will pro-
vide natural draft in the event of a power failure.
If the stove is installed below grade be sure the
vent termination should be at least 1 foot above grade.
CAUTION
Keep conlbustible materials (such
as grass, leaves, etc.) at least 3 feet
away from the flue outlet on the outside
of the building.
to combustibles
Fig. 9
9
P61A-2 Pellet Stove