User´s Guide Power Rail Booster
Power Rail Booster
Immunity to high-frequency discharge
Immunity to conducted interference
Immunity to conducted interference (Surge)
Climatic service environment
Ambient temperature with preferred mounting
position
Ambient temperature with other mounting position 0 °C to +45 °C
Storage temperature
Relative humidity
Mechanical ambience conditions
Vibration during operation
Vibration during transport
Type of protection
Dimensions
Preferred mounting position
Weight
Copyright © Siemens AG 2005 All rights reserved.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Testing following EN 61000-4-3:Frequency range 80
MHz - 1 GHz, test field intensity: 10 V/m at 80%
amplitude modulation with 1 kHz. Range 87 MHz
to108 MHz, 174 MHz to 230 MHz and 470 MHz to 790
MHz: 3V/m
Power and bus cables ± 2 kV (Burst) (EN61000-4-4)
Power cables ± 1 kV symmetrical (Surge)
Bus cables ± 2kV unsymmetrical (EN61000-4-5)
0 °C to +60 °C (IEC 68-2-1, IEC 68-2-2)
–40 °C to +70 °C (IEC 68-2-14)
<95 %, no condensation (IEC 68-2-30)
10 to 58 Hz, 0,075 mm displacement;
58 to 150 Hz, 9,8 m/s 2 (1 g) acceleration
(IEC 68–2–6)
5 to 9 Hz, 3,5 mm displacement;
9 to 500 Hz, 9,8 m/s 2 (1 g) acceleration
IP20
90,1x132x75 (WxHxD) with top hat rail 7,5 mm
90,1x132x82,5 (WxHxD) with top hat rail 15 mm
Horizontal installation on vertical wall
360g
6ES7 972-4AA02-0XA0
Version 12/2005