CP750 Firmware & Config Instructions
There will be several steps to this process:
1. Download software from LOFA web site
2. Remove panel from machine or at a minimum disconnect the 21 pin
connector from back of panel to connect tool.
3. Update Firmware in CPIO Circuit Board
4. Update Firmware in CP750 Display
5. Load Configuration into panel. (Configuration will be loaded onto the Display
and CPIO in one operation.) You would need to open an existing Config, make
a New Config with tool, or, use a Config sent to you by LOFA or OEM. Config
files are located on your computer in a folder which the tool automatically
saves to and points to:
C:\Users\Public\Documents\LOFA Industries\Configuration
It is best to save configurations sent to you in this folder location.
6. Reinstall panel
7. If used on a Mechanically Governed engine the tachometer will need to be
recalibrated.
IMPORTANT NOTES:
1. It is important to note that only one application at a time can be running
which utilizes the CANplus® adapter. !!
2. If there are any other devices connected to the CANbus they must be
disconnected from the panel during programming, I.E. Telemetry devices,
Skim modules, Etc.