13. Installation
13. Installation
13-1. Indoor unit
13-1. Indoor unit
Choosing the installation location
Overview of installation location requirements
4.92 inch (125 mm) or
more (recommended)
You can select the direction of draining
Maximum pipe height: 26.25 ft (8 m)
Maximum pipe length: 49.21 ft (15 m)
Make at least one round to
reduce noise and vibration.
AC018MNADCH
AC024MNADCH
AC030/036MNTDCH
Outdoor Unit
Outer wall
Indoor Unit
Cut insulation to have
rainwater drained
34
3.94 inch (100 mm) or
more (recommended)
4.92 inch (125 mm) or
more (recommended)
Drain hose hole
(left or right).
The actual units may look different from
the images depicted here.
Unit : ft (m)
9.84 (3)
98.43 (30)
65.62 (20)
9.84 (3)
164.04 (50)
98.43 (30)
Make a U-trap (A) on the pipe (which is
connected to the indoor unit) at outer
wall and cut the bottom part of the
CAUTION
insulation [about 0.39 inch (10 mm)] to
prevent rainwater from getting inside
through the insulation.
Checking and preparing accessories and tools
Accessories
Accessories in the indoor unit package
AC
MNADCH
Installation plate (1)
Installation plate (1)
Installation plate (1)