WATERPROOF SELF TESTING NON MAINTAINED EMERGENCY LUMINAIRES
TECHNICAL CHARACTERISTICS
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERIES (Pb)
BATTERY PROTECTION
INDICATIONS - CONTROLS
CHARGING TIME
MINIMUM AUTONOMOUS DURATION
LIGHT SOURCE
EMERGENCY ILLUMINATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
CONSTRUCTION MATERIALS
EXTERNAL DIMENSIONS
TYPICAL WEIGHT
GUARANTEE
GENERAL
These luminaires are used (ta 40 C) where
emergency light is needed. Each luminaire
must be connected permanently to the
mains power supply.
OPERATION DESCRIPTION
When the unit is connected to the mains power
supply (after connecting the battery) the
indicator LAMP FAULT – BATT. FAULT remains
OFF whereas the indicator POWER CHARGE
blinks to indicate that the batteries are charging.
When the batteries are fully charged this
indicator will light permanently. If this indicator
does not light then probably the battery has not
been connected. If the batteries are connected
and the indicator does not light then contact a
qualified service technician for assistance. The
charging procedure is monitored by a
microprocessor and is based on a 3 stage cycle
thus ensuring a fast and full charge of the
battery. The charge current is supplied by a high
efficiency switch mode power supply which
ensures perfect charging even during the
fluctuations of the mains power supply.
BATTERY CUTOFF
The unit enters this state during the power
supply failure and when the battery has been
Page 1 from 4
GRL-37/90/WP
POWER-CHARGE indicator, LAMP FAULT–BATT. FAULT indicator, TEST button
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
Thank you for your trust in our products
Olympia Electronics - European manufacturer
o
(for LED MODULE Specifications see page 4)
220-240V AC/50-60Hz
13.3W/14VA
12V/7Ah
From overcharge and deep discharge
<24 h
90 min.
White Power LEDs
3200lm
IP65
5 to 40 C
Up to 95%
Aluminum, ABS/PC, PC
307 x 100 x 350 mm.
6315gr.
3 years (1 year for the battery)
fully discharged. In this state the luminaire draws
the least power from the battery in order to
prevent
deep discharge.
MANUAL TESTING
Is accomplished by briefly (<1 sec.) pressing the
TEST button. This permits the user to test the
good operation of the luminaire's emergency
circuit. The unit simulates a power failure and the
lamps are lit using the batteries. This manual test
does not affect the automatic test.
DIMMING OPTION
When the luminaire is in emergency mode, with
corresponding pressings of the button, we can
choose the illumination of 100%, 50%, 33% or
turned off, either to increase the autonomy time
or not to consume the battery power
unnecessarily. This option is canceled when the
network is restored.
LAMP TESTING
The luminaire tests the good condition of the
lamps in emergency mode and warns the user
for probable malfunction. If a lamp is found faulty
then the LAMP FAULT indicator starts to blink. To
verify which lamp is faulty use the TEST button. If
GRL-37/180/WP