Delta Amplon TFM-RT-5/6K User Manual page 17

Transformer cabinet
Table of Contents

Advertisement

1. TFM-RT-8/10K Input/ Output cable selection:
Temperature Rating
90°C
In accordance with National Electrical Code (NEC), install a suitable conduit and
bushing.
NOTE :
2. Before connecting to the input/ output terminals, read this user manual tho-
roughly.
NOTE :
wer supply's output voltage setting.
TFM-RT-5/6K:
z
z
Plug the attached #10 AWG input power cord on the TFM-RT-5/6K into the power
supply.
TFM-RT-8/10K:
z
z
1. Remove the terminal block cover plate from the rear panel of the TFM-RT-8/10K
(a Phillips screwdriver is required). Refer to the figure below for the input/ output
connections. The copper terminals for the input and output cables are included.
a) Connect the black wire labeled L1 on the input power cable to the TFM-RT-
8/10K AC input terminal block labeled L1 and secure.
b) Connect the white wire labeled L2 on the input power cable to the TFM-RT-
8/10K AC input terminal block labeled L2 and secure.
c) Connect the green wire labeled G on the input power cable to the TFM-RT-
8/10K AC input terminal block's ground terminal and secure.
2. Connect the other end of the #6 AWG input power cable to the output terminal
block on the power supply and secure.
a) Connect the black wire labeled L on the input power cable to the power
supply's output terminal block labeled L and secure.
b) Connect the white wire labeled N on the input power cable to the power
TFM-RT-8/10K
#6 AWG (Cu)
Use copper wire only.
The TFM-RT's input voltage setting must be the same as the po-
Tightening Torque
1 4
Chapter 4
Installation
(For AC Wiring)
22 lb-in