Please refer to the block diagram and related information below for correct installa-
tion.
Input
GND

4.1 Installation Placement

The TFM-RT is ONLY intended to be installed in an indoor temperature controlled
environment that is free of conductive contaminants. DO NOT operate the unit in:
extremely dusty and/ or unclean areas, locations near heating devices, water or ex-
cessive humidity, or where the unit is exposed to direct sunlight. Select a location,
which will provide good air circulation for the unit at all times. Route power cords
so they cannot be walked on or damaged. The TFM-RT is not intended for use in
a computer room as defined in the Standard for the Protection of Electronic Com-
puter/ Data Processing Equipment ANSI/ NFPA 75.
Operating Temperature (Maximum): 0 ~ 40°C (32 ~ 104°F)
z
z
Operating Elevation: 0 ~ 2000m (0 ~ 6562ft)
z
z
Operating and Storage Relative Humidity: 95% (non-condensing)
z
z
Storage Temperature: -15 ~ 50°C (5 ~ 122°F)
z
z
Storage Elevation: 0 ~ 15000m (0 ~ 49213ft)
z
z
Amplon Transformer Cabinet

Chapter 4 : Installation

Breaker
L
Auxpower
N
Relay
Breaker
Relay
To Fan
To Relay
9
Breaker
Breaker
Output
Breaker
Breaker