Settings of External Device
(1) Startup "SIMATIC Manager" and create the new project. Set the optional project name and click [OK]. New
project is created.
(2) From the menu bar, select [Insert], [Station], [(Name of CPU type to use)] in this order.
(3) [(Name of CPU type to use)] is created in the project. Double-click [Hardware] of the name of CPU type to
use.
(4) When the [HW Config] screen displayed, open [(Name of CPU type to use)], [(RACK type to use)] in this
order from the left tree and select the base unit of the using model.
(5) Drag & drop the selected base unit to the upper right window. The rack figure is created in the window.
(6) Drag & drop the using power unit in the rack.
(7) Similarly, drag & drop the using CPU unit.
(8) When using CPUxxx-xDP, the [Properties - PROFIBUS interface DP] dialog box is displayed. In that case,
click [Cancel] and close the dialog box.
(9) Similarly, drag & drop the using link unit.
(10)Double-click the CPU unit dropped in the rack.
(11)When the [MPI port] setting dialog box is displayed, click [Properties].
(12)Click [Properties] as "MPI(1) 187.5 Kbps" is selected as default. The value entered in [Address] this time
becomes the Destination Node No. (PLC Address) you set in GP-Pro EX. The default is "2".
(13)To change the speed [Transmission rate] and the highest value of the node No. [Highest MPI address], click
the [Network Settings] tab.
Select [187.5Kbps] for [Transmission rate]. To change the highest value of the node No. (Highest MPI
address), check [Change] to allow you to select from the list.
(14)When you finish setting, click [OK] and close the dialog box.
(15)Close other dialog boxes similarly.