Figure 22 - TS2 Lonworks XBoard diagnostic Led
The below table show the checks it is possible to perform, the Led
to be checked and possible approaches to overcame the issues.
Function
Led and
normal
status
DL2 = OFF
Ethernet
Communication
TS2 application
DL6 = ON
running
DL1 = OFF
Data Base
DL6 = ON
present
DL2 = OFF
DL3 = OFF
LonWorks
DL5 = blink
Communicatio
n
31
Possible failure(s)
Approach
If DL2 = ON no
Check the Ethernet wiring.
Ethernet
Check the status of the
communication
network,
If DL6 = OFF no
Reset the TS2 device using
application running
Reset button.
If DL1 = ON the
Move the device from
device is running
manufacturing test to FW
the test application
application closing CN1.7.
If DL3 = ON no
Check if the supervision centre
application DB on
is up and running.
the device
Check if the TS2 device is
properly configured into EBI
If DL2 = ON
Check the Ethernet
Communication
communication first; without
failure with the
Supervision centre
supervision centre
communication there will not
be any DB download.
If DL5 steady OFF
The TS2 LonWorks Xboard is
broken and it must be
substituted.