FusionModule2000 Smart Modular Data Cente
Maintenance Guide
Impact on the System
The water leakage of the data center cannot be sensed.
Preparations
Procedure
Step 1 Replace the water detector.
1.
2.
3.
4.
Figure 6-43 Connecting a conversion cable to a water detector
Step 2 Replace a water detection cable.
1.
2.
Figure 6-44 Connecting a new water detection cable
(1) Conversion cable end B, connecting to
the water detection cable
Issue 03 (2019-12-04)
Material: water sensor
Skill requirement: hardware installation engineers
Remove the conversion cable at the conversion port for the water detector and
conversion cable.
Remove the communication cable from the water detector.
Connect a new water detector to the conversion cable.
Secure the new water detector.
Remove the faulty water detection cable from the port.
Install a new water detection cable.
Copyright © Huawei Technologies Co., Ltd.
(2) Water detection rope end A, connecting
to the conversion cable
6 Parts Replacement
75