Trane RTAF SE Series Installation Operation & Maintenance page 40

Air-cooled helical-rotary chillers
Table of Contents

Advertisement

General Electrical Recommendations
Table 21 – Electrical data
Compressor Data
RTAF
Quantity
Size
Standard Effi ciency
90
2
105
2
125
2
145
2
155
2
175
2
190
2
205
2
High Effi ciency
90
2
105
2
125
2
145
2
155
2
175
2
190
2
205
2
Notes:
1. Max power input per Fan for standard & high ambient
2. Max power input per Fan for low ambient
3. Maximum FLA per Fan for standard & high ambient and low ambient
4. Compressor maximum Amps under 400/3/50Hz
5. Compressor Start up Amps under 400/3/50Hz
Table 22 – Electrical data
Compressor Data
RTAF
Quantity
Size
Extra Effi ciency
90
2
105
2
125
2
145
2
155
2
175
2
190
2
205
2
High Seasonal Effi ciency
90
2
105
2
125
2
145
2
155
2
175
2
190
2
205
2
Notes:
1. Max power input per Fan for standard & high ambient
2. Max power input per Fan for low ambient
3. Maximum FLA per Fan for standard & high ambient and low ambient
4. Compressor maximum Amps under 400/3/50Hz
5. Compressor Start up Amps under 400/3/50Hz
40
Maximum Amps (4)
Cmpr 1
Cmpr 2
97
97
116
116
158
116
158
158
197
158
234
158
234
197
234
234
97
97
116
116
158
116
158
158
197
158
234
158
234
197
234
234
Maximum Amps (4)
Cmpr 1
Cmpr 2
97
97
116
116
158
116
158
158
197
158
234
158
234
197
234
234
90
90
105
105
147
105
147
147
182
147
206
147
206
182
206
206
Starting Amps (5)
Cmpr 1
Cmpr 2
144
144
180
180
259
180
259
259
291
259
354
259
354
291
354
354
144
144
180
180
259
180
259
259
291
259
354
259
354
291
354
354
Starting Amps (5)
Cmpr 1
Cmpr 2
144
144
180
180
259
180
259
259
291
259
354
259
354
291
354
354
90
90
105
105
147
105
147
147
182
147
206
147
206
182
206
206
Control Circuit Data
Disconnect switch Option
Power Cable Cross section
Min (mm²)
Max (mm²)
185
240
185
240
240
240
2x150
2x300
2x150
2x300
2x185
2x300
2x185
2x300
2x185
2x300
185
240
185
240
240
240
2x150
2x300
2x150
2x300
2x185
2x300
2x185
2x300
2x185
2x300
Control Circuit Data
Disconnect switch Option
Power Cable Cross section
Min (mm²)
Max (mm²)
185
240
185
240
240
240
2x150
2x300
2x150
2x300
2x185
2x300
2x185
2x300
2x185
2x300
185
240
185
240
240
240
2x150
2x300
2x150
2x300
2x185
2x300
2x185
2x300
2x185
2x300
RLC-SVX19A-E4

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rtaf xe seriesRtaf hse seriesRtaf he series

Table of Contents