Function block "Service functions
and general settings"
Function block "Service functions and general settings" is used to combine various
displays and setting functions that are of assistance in connection with commissioning
and service work. In addition, a number of extra functions are performed.
The service functions are independent of the type of plant.
25.1
Operating lines
Line
Function, parameter
161
Outside temperature simulation
162
Relay test
163
Sensor test
164
Test of H–contacts
165
Flow temperature setpoint
166
Resulting heating curve
167
Outside temperature for frost protection for the plant
168
Flow temperature setpoint for frost protection for the plant
169
Device number
170
Segment number
171
Flow alarm
172
Operating mode when terminals H1–M are bridged
173
Gain of locking signal
174
Pump overrun time
175
Pump kick
176
Winter- / summertime changeover
177
Summer- / wintertime changeover
178
Clock mode
179
Bus power supply
180
Outside temperature source
181
DC 0...10 V heat demand output U
194
Hours run counter
195
Controller's software version
196
Identification code of room unit
25.2
Display functions
25.2.1 Flow temperature setpoint
Displayed is the current flow temperature setpoint which is made up of the following
variables:
• Flow temperature setpoint in function of the composite outside temperature and the
heating curve
• Position of the knob for room temperature readjustments
• Parallel displacement (setting on operating line 72)
With demand-compensated control (plant types 4–x, 5–x, and 6–x), the display
shows ---.
Heating and D.h.w. Controller RVL481
25 Function block "Service functions and general settings"
Factory setting (range)
X
Unit
--.- (--.- / − 50...+50)
0 (0...10)
Display function
Display function
Display function
Display function
2.0 (--.- / 0...25)
15 (0...140)
0 (0...16)
0 (0...14)
--:-- (--:-- / 1:00...10:00)
hh:mm
0 (0...9)
100 (0...200)
6 (0...40)
min
0 (0 / 1)
25.03 (01.01...31.12)
dd:MM
25.10 (01.01...31.12)
dd:MM
0 (0...3)
A (0 / A)
A (A / 00.01...14.16)
130 (30...130)
Display function
Display function
Display function
CE1P2541en
20.05.2008
°C
°C
°C
%
°C