Temperature And D.h.w. Switching Differential - Siemens RVL481 Basic Documentation

Heating and d.h.w. controller
Table of Contents

Advertisement

Siemens
Building Technologies
19.3
D.h.w. temperature and d.h.w. switching
differential
The kind of d.h.w. storage tank temperature acquisition must be entered on operating
line 126.
In plant types x–5 without solar heating, select setting 0, 1, 2 or 3 on operating line
126, although d.h.w. heating with electric immersion heater does not require either
sensor or thermostat.
The storage temperature can be acquired via
• 1 or 2 sensors
• 1 or 2 thermostats
• 1 or 2 sensors with solar function; this activates function "Solar d.h.w. charging".
If temperature sensors are used, the switch-on / off temperature for charging is deter-
mined as follows:
SD
BW
ON
OFF
T
T
= T
OFF
BWw
ON
ON
D.h.w. charging ON
OFF D.h.w charging OFF
SD
Switching differential of d.h.w. charging
BW
T
Switch-on temperature
ON
T
Switch-off temperature
OFF
If the d.h.w. storage tank is equipped with thermostats, the switch-on / off temperature
is determined by the thermostats.
Determination of the switch-on temperature (start of d.h.w. charging):
Operating
Measurement
line 126
0
1 sensor
1
2 sensors
2
1 thermostat
3
2 thermostats
4
1 sensor, solar
d.h.w. heating
5
2 sensors, solar
d.h.w. heating
Determination of the switch-off temperature (end of d.h.w. charging):
Operating line 126 Measurement
0
1 sensor
1
2 sensors
2
1 thermostat
3
2 thermostats
4
1 sensor, solar
d.h.w. heating
5
2 sensors, solar
d.h.w. heating
From the 2 tables above, it is obvious that when using 2 sensors, it is irrelevant which
of the 2 sensors is fitted at the top and which at the bottom of the d.h.w. storage tank.
Heating and D.h.w. Controller RVL481
19 Function block "D.h.w. storage tank"
T
BWx
T
D.h.w temperature setpoint
BWw
T
D.h.w. temperature
BWx
T
Measured value d.h.w. storage tank sensor B31
BWx1
T
Measured value d.h.w. storage tank sensor B32
BWx2
Switching criterion
T
< (T
– SD
BWx1
BWw
T
< (T
– SD
BWx1
BWw
Thermostat contact B31 closed
Both thermostat contacts B31 and B32 closed
T
< (T
– SD
BWx1
BWw
T
< (T
– SD
BWx1
BWw
Switching criterion
T
> T
BWx1
BWw
T
> T
and T
BWx1
BWw
Thermostat contact B31 open
Both thermostat contacts B31 and B32 open
T
> T
BWx1
BWw
T
> T
and T
BWx1
BWw
)
BW
) and T
< (T
– SD
BW
BWx2
BWw
)
BW
) and T
< (T
– SD
BW
BWx2
BWw
> T
BWx2
BWw
> T
BWx2
BWw
71/118
CE1P2541en
20.05.2008
)
BW
)
BW

Hide quick links: