Function Block "Space Heating; Operating Lines; Eco Function; Compensating Variables And Auxiliary Variables - Siemens RVL481 Basic Documentation

Heating and d.h.w. controller
Table of Contents

Advertisement

36/118
Siemens
Building Technologies
10

Function block "Space heating"

This function block performs the ECO function, the optimization functions with boost
heating and quick setback, as well as the room influence.
10.1

Operating lines

Line
Function, parameter
61
Heating limit for NORMAL heating (ECO day)
62
Heating limit for REDUCED heating (ECO night)
63
Building time constant
64
Quick setback
65
Room temperature source
66
Type of optimization
67
Maximum heating up time
68
Maximum early shutdown
69
Maximum limitation of room temperature
70
Gain factor of room influence
71
Boost of room temperature setpoint
72
Parallel displacement of the heating curve
73
Heating curve slope
10.2

ECO function

The ECO function controls space heating depending on demand. It gives consideration
to the progression of the room temperature depending on the type of building construc-
tion as the outside temperature varies. If the amount of heat stored in the house or
building is sufficient to maintain the room temperature setpoint currently required, the
ECO function will switch the heating off.
When using the ECO function, the heating system operates only, or consumes energy
only, when required.

10.2.1 Compensating variables and auxiliary variables

As compensating and auxiliary variables, the ECO function takes into account the de-
velopment of the outside temperature and the heat storage capacity of the building.
The following variables are taken into consideration:
• The building time constant: this is a measure of the type of building construction and
indicates how quickly the room temperature would change if the outside temperature
was suddenly changed. The following guide values can be used for setting the building
time constant:
10 hours for light building structures
25 hours for medium building structures
50 hours for heavy building structures
• The actual outside temperature (T
• The composite outside temperature (T
the actual outside temperature, and
the outside temperature filtered by the building time constant
Compared with the actual outside temperature, the composite outside temperature is
attenuated. Hence, it represents the effects of short-time outside temperature varia-
tions on the room temperature as they often occur during intermediate seasons
(spring and autumn)
• The attenuated outside temperature (T
outside temperature by the building time constant. This means that, compared with the
actual outside temperature, the attenuated outside temperature is considerably damp-
ened. This ensures that no heating will take place in the summer when, under normal
Heating and D.h.w. Controller RVL481
10 Function block "Space heating"
Factory setting (range)
17.0 (--.- / −5.0...+25.0)
5.0 (--.- / −5.0...+25.0)
00:00 (00:00...42:00)
)
A
), which is the mean value of:
AM
): it is generated by filtering twice the actual
AD
Unit
°C
°C
20 (0...50)
h
1 (0 / 1)
A (0 / 1 / 2 / 3 / A)
0 (0 / 1)
hh:mm
0:00 (0:00...6:00)
h:mm
--.- (--.- / 0...35)
°C
4 (0...20)
5 (0...20)
°C
0.0 (−4.5...+4.5)
°C
0 (0...2)
CE1P2541en
20.05.2008