en | B926F Fire Keypad operating instructions
9
B926F Fire Keypad operating instructions
This keypad is a full-function system controller and
annunciator. The illuminated keypad has a display and a
sounder that emits distinct condition tones to alert you
to fi re alarm, fi re trouble, or fi re supervisory events as
they occur. In conjunction with the display and sounder,
seven status indicators provide the following system status
information as described below.
Required: Mount this document in view of the fi re
keypad.
Overview
Status indicators
The Status indicators provide a quick
visual reference of the system status.
Ready to arm
Lights when the system is ready
to turn on (arm).
On (armed)
Lights when the system is on
Lights when a gas alarm exists.
Lights to indicate the control
panel has AC power.
Fire function keys
ACK. Press to acknowledge the system alarm or trouble condition.
SILENCE. Press to silence fi re alarm or trouble.
RESET. Press to reset devices such as smoke detectors.
DRILL. Press and hold to initiate fi re drill.
Navigation and number keys
The keypad includes keys for navigating and entering passcodes:
PREV and NEXT. Use to scroll through menus or menu selections.
ENTER. Use to complete the entry of your passcode or other
numbers, or to answer Yes to a keypad request.
backspace when you enter names and numbers.
ESC. Use to exit from menus and functions, or use as a
backspace when you enter names and numbers.
Number keys. Use to enter passcodes or other numbers and
letters.
Operation
Normal operation
When in normal operation and off (disarmed), the keypad shows programmed idle text, such as *Fire System*, or System
Ready.
Fire Alarm operation
When a fi rm alarm occurs, the Fire indicator lights, and the keypad emits a pulsing high-pitched fi re tone (____ ____ ____). The
tone sounds for the duration set by your security company. The keypad shows the fi rst point that entered alarm and its area.
Press ACK to acknowledge the alarm. The keypad shows the next point in alarm, if applicable. Press SILENCE to silence the
alarm.
Fire Trouble operation
When a trouble condition occurs (such as wiring for a point is cut or AC power fails), the keypad sounder activates briefl y
approximately every six seconds. The Trouble indicator lights and the keypad shows the highest priority trouble. Press ACK
to acknowledge the trouble. To view and acknowledge additional system or point troubles, press NEXT repeatedly.
Fire Supervisory operation
When a supervisory condition occurs, the sounder activates briefl y approximately every six seconds. The Supervisory
indicator lights and the keypad shows a fi re supervisory message. Press ACK to acknowledge the supervisory condition. To
view and acknowledge point supervisory conditions, press NEXT repeatedly.
Silence and reset
Alarm or Trouble silence. Press SILENCE and enter your passcode.
Detector reset. Press RESET and enter your passcode (if required). You can also use [CMD][4][7], or the Menu to
reset detectors.
2019-12 | 06 | F.01U.304.001
Alphanumeric display
GAS
(armed).
ACK
Gas
SILENCE
RESET
Power
DRILL
Local Service Representative
Name
Address
Phone
Fire Status indicators
The Fire Status indicators provide
a quick visual reference of the fi re
system status.
A1 Lobby
System Ready
UL Installation manual
Fire
Lights when a fi re alarm
condition exists; turns off when
all fi re alarm points return to
normal.
Silenced
Lights when a fi re alarm condition
is silenced; turns off when a
user presses the RESET button
or if another fi re alarm condition
appears.
Supervisory
Lights when any point
programmed as supervisory is
not normal; turns off when all
supervisory points return to
normal.
Trouble
Lights when a trouble condition
exists.