1. Insert and secure the electrode in the test vessel
only with the seal ring supplied.
2. Mount the test vessel on the extension connector.
3. Connect the TDS line.
Steam out-
t/h
put
Conductivity
mm
electrode
(Dim. a)
1. Fit intermediate flange
connector for the safety connection.
Safety connection:
for 0.26 and 0.44 t/h:
for 0.7 t/h:
2. Install the safety valve vertically.
3. Connect discharge pipe
.
A
4. Check the connections for possible leaks.
Test pressure:
Note
Damage due to excessively high test pressure is
excluded from our warranty.
0.26
0.44
400
450
with gaskets
on the
D
C
DN 65 PN 16
DN 80 PN 16
and the dewatering line
B
4.8 bar/0.48 MPa
0.7
500