Midea M2OE-14HFN1-Q Service Manual page 32

Super dc inverter multi type
Table of Contents

Advertisement

Service manual
Cooling mode:
Heating mode:
10.5.5 Indoor / outdoor units communication protection
If the indoor units cannot receive the feedback signal from the outdoor units for 2 minutes, the AC will stop
and display the failure.
10.5.6 High condenser coil temp. protection.
10.5.7 Outdoor unit anti-freezing protection
When T2<4 ℃ for 250 seconds or T2<0 ℃ , the indoor unit capacity demand will be zero and resume to
normal when T2>8 ℃ and the time of protection is no less than 3 minutes.
10.5.8 Oil return
Running rules:
1. If the compressor frequency keeps lower than setting frequency for setting time, the AC will rise the
frequency to setting frequency for setting time and then resume to former frequency.
2. The EXV will keep 300p while the indoor units will keep the current running mode.
If the outdoor ambient is higher than setting frequency during the oil return, the AC quit oil return.
32
T4
T4
T3
Off
Decrease
Hold
Resume
CoolZone5
CoolZone4
CoolZone3
CoolZone2
CoolZone1
HeatZone4
HeatZone3
HeatZone2
HeatZone1
Multi DC inverter R410A. Outdoor unit
DM16-01.01.11-01en

Advertisement

Table of Contents
loading

Table of Contents