2.4

Binary Inputs

The 2 binary inputs BI-1 and BI-2 operate across a wide input-voltage range. Logic 1 (high) is a voltage level
from DC 24 V to 250 V, -20 %, +15 %, with polarity-reversal protection and a pickup threshold of 18 V. In
exceptional cases, for example, with long unshielded lines and a disturbing influence, the pickup threshold
can be set to about 75 V (see
Logic 0 (low) is a voltage level below the set pickup threshold. When the corresponding binary input is acti-
vated, the corresponding yellow LEDs (BI-1, BI-2) light up.
Table 2-6
Binary Input 1 BI-1
Active
If the optical fiber or RS232 is being used for communication, the LEDs K1 and K2 indicate the state of the
binary inputs on the remote station.
Accessories, Binary signal transmitter 2-channel, Manual
C53000-G9050-C607-1, Edition 09.2019
Table 2-7
and

Binary Inputs

Binary Input 2 BI-2
Active
Figure
2-3).
LED BI-1
LED BI-2
Lit
Device Structure
2.4 Binary Inputs
LED K1
Remote
station
Lit
LED K2
Remote
station
19