Technical data
General unit data
Environmental
conditions
8/15
Building Technologies Division
Mains voltage
- Only with LGA63...
Mains frequency
Power consumption
Perm. mounting position
Degree of protection
Safety class
Input current at terminal 1
Permissible cable lengths
Detector cable, laid separately
Perm. electrical rating
- Terminal 4
- Terminal 5
- Terminal 6
- Terminal 7
- Terminal 8
- Terminal 9
- Terminal 10
Cable length terminal
Weight
Storage
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Transport
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Operation
Climatic conditions
Mechanical conditions
Temperature range
Humidity
Installation altitude
Caution!
Condensation, formation of ice and ingress of water are not permitted!
If this is not observed, there is a risk of loss of safety functions and a risk of
electric shock.
AC 220 V 15 %...AC 240 V +10 %
AC 100 V –15 %...AC 110 V +10 %
AC 230 ±10 %
50...60 Hz ±6 %
3 VA
Optional
IP40 (when integrated)
I (burner control with plug-in base)
Max. 5 A
Max. 3 m with 100 pF/m line capacitance
Max. 4 A
Max. 1 A
Max. 2 A
Max. 2 A
Max. 4 A
Max. 0,1 A
Max. 1 A
20 m at 100 pF/m
Approx. 180 g
DIN EN 60721-3-1
Class 1K3
Class 1M2
-20...+60 °C
<95 % r.h.
DIN EN 60721-3-2
Class 2K2
Class 2M2
-50...+60 °C
<95 % r.h.
DIN EN 60721-3-3
Class 3K5
Class 3M2
0...+60 °C
For LGA41.173A27 and LGA52.171B27:
-20...+60 °C
<95 % r.h.
Max. 2,000 m above sea level
CC1N7418en
21.06.2016

Advertisement