Download Print this page
Tense DT-96 Manual

Tense DT-96 Manual

Auto-tune pid temperature controller

Advertisement

Quick Links

AUTO-TUNE PID TEMPERATURE CONTROLLER
General Specification:
 µP based, PID temperature controller with OUT and ALARM outputs
 Auto-tuning for PID parameters
 Sensor type: T/C (J,K,T,S,R), Pt100, selectable, multi-input
 Selectable control type: P, PI, PD, PID or ON-OFF
 Automatic "Overshoot" elimination in PID mode
 "Anti-windup"
 Upper and Lower limit for SET and ALARM settings
 Selectable relative, absolute or band alarm
 ON-delay for OUT in cooling mode
 Displays SET and PROCESS values
 Cold-junction compensation for T/C
 Line compensation for Pt100
 Excellent linearity with
 Input "Offset" feature
 Password protection
 High accuracy
 EEPROM memory to store settings
 Optional SSR output
 Easy connection with plug-in connectors
no: normally open
nc: normally closed
Warning: if 2 wire Pt100 is used, connect
compansation lead to measuring lead
(DT-96: 17-18,DT-72: 13-14,
DT-48: 10-11)
Alarm
TENSE Elektronik
o
C/mV and
3
100 ... 240VAC
50/60Hz 6VA
4
no
5
13
6
Out
14
nc
7
15
T/C
no
8
Pt100
Out & Alarm:
9
250V
AC
max.2A
resistive load
nc
10
DT-96 / DT-72 / DT-48
o
C/ look-up tables
CONNECTION
1
100 ... 240VAC
50/60Hz 6VA
2
no
3
Out
4
nc
5
Alarm
6
7
Out & Alarm;
250V
AC
max.2A
resistive load
1
3
4
5
6
10
7
11
8
12
T/C
9
Pt100
10
100 ... 240VAC
50/60Hz 6VA
no
17
Out
18
nc
19
T/C
no
Pt100
Alarm
Out & Alarm;
250VAC
nc
max. 2A
resistive load

Advertisement

loading
Need help?

Need help?

Do you have a question about the DT-96 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Tense DT-96

  • Page 1 DT-96 / DT-72 / DT-48 AUTO-TUNE PID TEMPERATURE CONTROLLER General Specification:  µP based, PID temperature controller with OUT and ALARM outputs  Auto-tuning for PID parameters  Sensor type: T/C (J,K,T,S,R), Pt100, selectable, multi-input  Selectable control type: P, PI, PD, PID or ON-OFF ...
  • Page 2 TECHNICAL SPECIFICATION  Dimensions : DT-96:96x96, DT-72:72x72, DT-48:48x48mm  Display : 4 Digits 7 Segment (PV), 4 digits 7 Segment (SV)  Sensor Type : J,K,T,S,R type T/C, Pt100 selectable  Measuring Scale : -100 .. 600 C, J type T/C, (Inpt=J) -100 ..
  • Page 3 (1) When sensor type is changed, Up.L, Lo.L, H.Set or A.Set may be set to a new value End Prog. automatically, if any of them violates measuring scale of t he selected sensor. (2) ON-OFF control is the only option for Cooling function (3) If sensor type is selected as Pt.0. TENSE Elektronik...
  • Page 4 Td: Derivative time; Set in minutes. If set to 0, derivative part is OFF. Determines how sensitive the controller is to changes of the offset between SET point and the process value. If set too high, process value may oscillate or overshoot. TENSE Elektronik...

This manual is also suitable for:

Dt-72Dt-48