Attention, Risk of,
Danger, Warning
•
Dimensions
•
Panel Cut-out
•
Display
•
Sensor Type
•
Measuring Scale
•
Resolution
•
Accuracy
•
Control Form
•
Control Output
•
Heat SET
•
Heat Hysteresis
•
Proportional Band
•
Integral Time
•
Derivative Time
•
Control Period
•
Offset
•
Heating/Cooling
•
Cold. Junc. Comp.
•
Line Comp.
•
Sensor Failure
•
Supply Voltage
•
Power Consumption : < 8VA
•
Humidity
•
Altitude
•
EMC
•
Safety
•
Protection Class
•
Temperature Spec.
•
Weight
•
Torque for screwing : Max. 0.5 N.m
WARNING:
if 2 wire Pt100 is used, connect compensation lead to measuring lead:
(DT-96EM :17-18, DT-72EM: 13-14,
DT-48EM: 10-11)
AUTO-TUNE PID TEMPERATURE CONTROLLER
High Voltage,
Risk of Electric Shock
TECHNICAL SPECIFICATION
: DT-96EM:96x96, DT-72EM:72x72, DT-48EM:48x48mm
: DT-96EM:91x91, DT-72EM:68x68, DT-48EM:45,5x45,5mm
: 4 Digits 7 Segment (PV), 4 digits 7 Segment (SV)
: J,K,T,S,R type T/C, Pt100 selectable
o
: -100..600
C, J type T/C (Inpt=J),
o
-100..1300
C, K type T/C (Inpt=k), -100.0..999.9
o
-100..400
C, T type T/C (Inpt=t),
o
0..1750
C, S type T/C (Inpt=S)
o
-100..600
C, Pt100, (Inpt=Pt)
o
o
: ± 1
C or ± 0.1
: ± 1 % (Over full scale)
: ON-OFF or P, PI, PD, PID - selectable
: Relay (NO + NC), 250VAC, 2A, resistive load / SSR (12Vdc, 20mA) -
selectable
: Lower Limit .. Upper Limit
: 0 .. 50 / 0.0 .. 50.0
o
: 5 .. 150
C (Pb.C)
: 0:00 .. 30:00 min:sec. (OFF if set to 0:00)
: 0:00 .. 10:00 min:sec. (OFF if set to 0:00)
: 1 .. 200 sec. (Ct)
o
: -100..+100
C / -100.0 .. +100.0
: Only heating function
o
: 0 .. 50
C (T/C)
: 10 Ohm max. (3 wire Pt100)
: OUT output is active according to P.Err and Ct parameters in case of
sensor failure, measurement out of range or hardware fails to measure
input signal (OUT output is OFF if Perr is 0).
: 100..240VAC, 50-60Hz - or
(Optional; 24VDC/AC, maximum isolation voltage: 40VAC)
: < 70% (non-condensing)
: < 2000 m
: EN 61000-6-1, EN 61000-6-3 (Only light industrial environment)
: EN 61010-1; Pollution degree 2, measurement category II
(Only light industrial environment, double/reinforced isolated)
: IP20; according to EN 60529
: Operating: 0 .. 50
: < 0.5 kg
DT-96EM / DT-72EM / DT-48EM
Double / Reinforced
Insulation
-100.0 .. 600.0
-100.0 .. 400.0
0 .. 1750
-100.0 .. 600.0
C
o
C (H.Set)
o
C (H.hys); PID is active if set to 0
o
C (oFFS)
o
o
C, Storage -10
C .. 60
NOT
CE Mark
Litter
o
C, J type T/C (Inpt=J.0)
o
C, K type T/C, (Inpt=k.0)
o
C, T type T/C (Inpt=t.0)
o
C, R type T/C (Inpt=r)
o
C, Pt100, (Inpt=Pt.0)
o
C (no icing)