  • Page 1 Active Parallel Multi-Function Filter AFQevo INSTRUCTION MANUAL (M102B01-03-18A)
  • Page 2 AFQevo Instruction Manual...
  • Page 3: Safety Precautions

    DISCLAIMER CIRCUTOR, SA reserves the right to make modifi cations to the device or the unit specifi ca- tions set out in this instruction manual without prior notice. CIRCUTOR, SA on its web site, supplies its customers with the latest versions of the device specifi cations and the most updated manuals. www.circutor.com CIRCUTOR, recommends using the original cables and accessories that are supplied with the device.
  • Page 4: Table Of Contents

    3�6�1�- 30 A AFQevo: AFQe-xxx-030M �������������������������������������������������������������������������������������������������������21 3�6�2�- 100A AFQevo RACK-TYPE : AFQe-xxx-100R ��������������������������������������������������������������������������������22 3�6�3�- 100 A AND 200 A AFQevo CABINET-TYPE : AFQe-xxx-100C AND AFQe-xxx-200C ������������������23 3�7�- CONNECTION DIAGRAMS ��������������������������������������������������������������������������������������������������������������������27 3�7�1�- 4-WIRE CONNECTION AND CURRENT MEASUREMENT ON THE MAIN SIDE� ��������������������������27 3�7�2�- 4-WIRE CONNECTION AND CURRENT MEASUREMENT ON THE LOAD SIDE�...
  • Page 5 10�2�1�- 30 A AFQevo : AFQe-xxx-030M ����������������������������������������������������������������������������������������������������� 85 10�2�2�- 100 A AFQevo RACK-TYPE: AFQe-xxx-100R ����������������������������������������������������������������������������� 87 10�2�3�- 100 A AND 200 A AFQevo cabinet-type : AFQe-xxx-100C AND AFQe-xxx-200C ���������������������� 90 10�3�- FUSES ( Models AFQe-xxx-100C and AFQe-xxx-200C) ��������������������������������������������������������������������� 90 11�- TECHNICAL FEATURES ������������������������������������������������������������������������������������������������������������������������������� 91 12�- TECHNICAL SERVICE ����������������������������������������������������������������������������������������������������������������������������������...
  • Page 6: Revision Log

    AFQevo REVISION LOG Table 1: Revision log� Date Revision Description 12/16 M102B01-03-16A Initial Version Changes in sections: 01/17 M102B01-03-17A 1.2.- 2.- 3.1. - 3.2.1. - 3.4. - 3.5. - 3.6. - 3.8. - 4.5. - 4.6. - 6.13.- 6.14.- 7.1. - 7.2.
  • Page 7: 1�- Verification Upon Reception

    Check that it has been delivered with the following: - Instruction manual - Communication cable for connecting devices in parallel. - Trim panel (Cabinet-type AFQevo : AFQe-xxx-100C and AFQe-xxx-200C). - Bag with 5 rubber caps (AFQe-xWF-030M). e) Perform an external and internal visual inspection of the device prior to connecting it.
  • Page 8 When unpacking the device, pay attention to prevent damaging the device if you are using cut- ting tools, such as cutters, scissors or knives. AFQevo 100 A (AFQe-xxx-100C) and 200 A (AFQe-xxx-200C) cabinets are delivered with the base removed to enable them to be transported with a pallet jack or similar.
  • Page 9: 1�3�- Storage

    AFQevo 1.3.- STORAGE The device should be stored according to the following recommendations:  Avoid placing them on uneven surfaces.  Do not store them in outdoor areas, humid areas or areas exposed to splashing wa- ter.  Avoid hot spots (maximum ambient temperature: 50ºC)  Avoid salty and corrosive environments.
  • Page 10: 2�- Product Description

    - Parallel installation of up to 100 devices. - EMI filters, optional. - LCD touch display, to view the parameters. - RS-485 and Ethernet communications. - Wall enclosure. Table 3:Relation of models AFQevo of 30A� 3 Wires 4 Wires Model EMI filter...
  • Page 11 - LCD touch display, to view the parameters. - RS-485 and Ethernet communications. Rack or cabinet-type enclosure� - Protection module (Model AFQe-xxx-100C) - EMI filters included (Model AFQe-xxx-100C) Table 4:Relation of models AFQevo of 100A� Operation Type 3 Wires 4 Wires...
  • Page 12 - Parallel installation of up to 100 devices.. - LCD touch display, to view the parameters. - RS-485 and Ethernet communications. - Cabinet-type enclosure� - Protection module included. - EMI filters included Table 5:Relation of models AFQevo of 100A� Operation 3 Wires 4 Wires Protection Model...
  • Page 13: 3�- Device Installation

    AFQevo 3�- DEVICE INSTALLATION 3.1.- PRELIMINARY RECOMMENDATIONS The device installation and the maintenance operations must only be car- ried out by authorised and qualified personnel. In order to use the device safely, it is critical that individuals who handle it follow...
  • Page 14: 3�2�- Installation Location

    Make sure there are no power factor correction devices installed in the same main as the AFQevo. If there are any compensation devices, these must be detuned in order to avoid interference between them and the AFQevo. 3�2�1�- VENTILATION REQUIREMENTS 3�2�1�1�- 30A AFQevo...
  • Page 15 With deflectors installed. 3�2�1�3�- AFQevo cabinet-type: AFQe-xxx-100C and AFQe-xxx-200C The cabinet-type AFQevo uses a forced ventilation cooling system, with an air inlet on the front panel and an air outlet at the back of the device. The ventilation grille at the top must not be blocked, leaving enough space to the ceiling to allow the heat to dissipate.
  • Page 16: 3�3�- Storage For Long Periods

    STOP mode 3.4.- INSTALLATION 3�4�1�- 30 A AFQevo The AFQevo of 30A has a number of holes on the top and bottom of the device, Figure 4, facilitate transport and installation of the device. These holes can be used as attachment points for external manipulation tools, or a bar (not included) can be passed through them to improve transport and installation of the device.
  • Page 17: 3�4�2�- 100 A Afqevo Rack-Type: Afqe-Xxx-100R

    2�- Open or remove the door at the front of the cabinet. 3�- Place the AFQevo on the cabinet’s rails or shelves. Make sure that they are suitable for the weight of the device; use cross braces if necessary.
  • Page 18: 3�4�3�- 100 A And 200 A Afqevo Cabinet-Type: Afqe-Xxx-100C And Afqe-Xxx-200C

    AFQevo 3�4�3�- 100 A AND 200 A AFQevo CABINET-TYPE: AFQe-xxx-100C AND AFQe-xxx-200C The 100 A (AFQe-xxx-100C) and 200 A (AFQe-xxx-200C) models of the AFQevo are free-standing cabinets with 4 bearing supports on the floor. The mounting surface must be solid, support the device’s weight and be level. The cabinet must never be welded to the floor using arc welding, as this may destroy the electronic components.
  • Page 19: 3�5�- Connection

    The recommended minimum cross-sections are: AFQe-xxx-100C : 35 mm AFQe-xxx-200C : 70 mm Ensure that the AFQevo is earthed correctly to prevent the risk of electric shock. To measure the current, class 0�2S transformers of the TC or TCH series are recommended.
  • Page 20 AFQevo If local regulations require the use of earth leakage protection devices, only DC sensitive RCD (RCD type B) should be used with AFQevo. Active filters work internally with DC currents, and, in case of failure, the DC currents may produce malfunction on type A RCD devices.
  • Page 21: 3�6�- Device Terminals

    3�6�1�- 30 A AFQevo: AFQe-xxx-030M The connection terminals of the AFQe-xxx-030M model are located on the lower face of the device. The AFQevo model without an EMI filter (AFQe-xWS-030M) has a terminal cover on the main connection terminals. Figure 8: Terminal cover (AFQe-xWS-030M)� Remove the terminal cover before connecting the device.
  • Page 22: 3�6�2�- 100A Afqevo Rack-Type : Afqe-Xxx-100R

    AFQevo 9 10 11 12 4 5 6 Figure 9:AFQevo terminals without EMI filter (AFQe-xWS-030M). 9 10 11 12 4 5 6 Figure 10:AFQevo terminals with EMI filter (AFQe-xWF-030M). Note : AFQe-xWF-030M device includes rubber caps to cover grid terminal screws, if required...
  • Page 23: 3�6�3�- 100 A And 200 A Afqevo Cabinet-Type : Afqe-Xxx-100C And Afqe-Xxx-200C

    Figure 11:AFQevo terminals part 1 (AFQe-xxx-100R)� Figure 12:AFQevo terminals part 2 (AFQe-xxx-100R)� 3�6�3�- 100 A AND 200 A AFQevo CABINET-TYPE : AFQe-xxx-100C AND AFQe-xxx-200C There are sliding windows at the bottom of the cabinet so that the connection wiring can be slotted inside, .
  • Page 24 AFQevo Screws Figure 14: Front cover screws� When the front cover has been opened, access the terminals from Table 12 Table 12:List of terminals� Device terminals 1: S1, Current input L1 7: L1, Main connection L1 2: S2, Current input L1...
  • Page 25 AFQevo AFQe-4WF-200C AFQe-3WF-200C 1 2 3 4 5 6 1 2 3 4 5 6 Floor Figure 16: AFQe-xxx-200C terminals part 1� Note: The dimensions of are in mm. Figure 16 The L1 (7), L2 (8) and L3 (9) power cables are connected to a terminal strip, protected by a cover.
  • Page 26 6: S, 4 5 6 Figure 17: AFQevo terminals part 2 (AFQe-xxx-100C and AFQe-xxx-200C)� The connection cables should be passed through the cable grommet at the bottom of the cabinet. We recommend separating the communications cables from the power cables, to reduce interference.
  • Page 27: 3�7�- Connection Diagrams

    AFQevo 3.7.- CONNECTION DIAGRAMS 3�7�1�- 4-WIRE CONNECTION AND CURRENT MEASUREMENT ON THE MAIN SIDE� P2 P1 S1 S2 S1 S2 S1 S2 MCCB CARGA / LOAD RED/ MAIN P2 S1 Figure 19: Three-phase measuring with 4-wire connection and current measurement on the main side�...
  • Page 28: 3�7�2�- 4-Wire Connection And Current Measurement On The Load Side

    AFQevo 3�7�2�- 4-WIRE CONNECTION AND CURRENT MEASUREMENT ON THE LOAD SIDE� P2 P1 S1 S2 S1 S2 S1 S2 MCCB CARGA / LOAD RED/ MAIN P2 S1 Figure 20: Three-phase measuring with 4-wire connection and current measurement on the load side�...
  • Page 29: 3�7�3�- 3-Wire Connection And Current Measurement On The Main Side

    AFQevo 3�7�3�- 3-WIRE CONNECTION AND CURRENT MEASUREMENT ON THE MAIN SIDE� P2 P1 S1 S2 S1 S2 S1 S2 MCCB CARGA / LOAD RED/ MAINS P2 S1 Figure 21: Three-phase measuring with 3-wire connection and current measurement on the main side�...
  • Page 30: 3�7�4�- 3-Wire Connection And Current Measurement On The Load Side

    AFQevo 3�7�4�- 3-WIRE CONNECTION AND CURRENT MEASUREMENT ON THE LOAD SIDE� P2 P1 S1 S2 S1 S2 S1 S2 MCCB CARGA / LOAD RED/ MAINS P2 S1 Figure 22: Three-phase measuring with 3-wire connection and current measurement on the load side�...
  • Page 31: 3�7�5�- 3-Wire Connection And 2 Current Transformers On The Main Side

    AFQevo 3�7�5�- 3-WIRE CONNECTION AND 2 CURRENT TRANSFORMERS ON THE MAIN SIDE� P2 P1 S1 S2 S1 S2 S1 S2 MCCB CARGA / LOAD RED/ MAINS Figure 23: Three-phase measuring with a 3-wire connection and 2 current transformers on the main side�...
  • Page 32: 3�7�6�- 3-Wire Connection And 2 Current Transformers On The Load Side

    AFQevo 3�7�6�- 3-WIRE CONNECTION AND 2 CURRENT TRANSFORMERS ON THE LOAD SIDE� P2 P1 S1 S2 S1 S2 S1 S2 MCCB CARGA / LOAD RED/ MAINS Figure 24: Three-phase measuring with a 3-wire connection and 2 current transformers on the load side�...
  • Page 33: 3�8�- Parallel Connection Of 2 To 100 Active Filters

    AFQevo 3.8.- PARALLEL CONNECTION OF 2 TO 100 ACTIVE FILTERS The AFQevo devices can be arranged in parallel to increase the available filtering power. Up to 100 devices can be arranged in parallel, either of the 30A or 100A models. In the case of installations with devices in parallel, a device must be defined as the “master”, while all others will have “slave” devices functions. The “master” will be responsible for measuring the network parameters, so only the current transformers will be connected to it.
  • Page 34: 3�8�1�- Connecting Individual Devices

    AFQevo 3�8�1�- CONNECTING INDIVIDUAL DEVICES Note: CIRCUTOR has devices that are factory-configured as slaves to enable devices to be connected in parallel. To connect multiple individual devices in parallel, follow these steps: 1�- Select the device that will operate as the “master”. Note: Devices that are factory-configured as “slaves” cannot perform this function.
  • Page 35: 3�8�2�- Connecting Cabinets

    AFQevo Note: The communication cable must be a CAT 5 cable or higher. Maximum cable length 3 metres. 5�- Configure the installation in the “master” device (see “7.- CONFIGURATION” 6.- Complete the configuration of the “slave” devices (see “7.- CONFIGURATION” 3�8�2�- CONNECTING CABINETS Note: The 200 A (AFQe-xxx-200C) devices are composed of 2 100 A devices in parallel. They are connected and configured in parallel in the factory.
  • Page 36 AFQevo Connect them using the communication cables ( Table 16 Table 16: Communication cable, devices in parallel� Communication cable RJ11 connector Pinout 1: Not connected. 2: CAN A 3: CAN B 4: Not connected. Note: The communication cable must be a CAT 5 cable or higher. Maximum cable length 3 metres.
  • Page 37: 4�- Operation

    AFQevo 4�- OPERATION 4.1.- HARMONICS Non-linear loads such as: rectifiers, inverters, variable speed drives, ovens, etc., absorb peri- odic non sine-wave currents from the main. These currents are composed of a fundamental frequency component, rated at 50 or 60 Hz, plus a series of overlapping currents, with frequencies that are multiples of the fundamental frequency; they are defined as HARMONICS. Fundamental Harmonic ware Harmonic ware Distorted ware Ware 5th order 250 Hz...
  • Page 38: 4�1�2�- Most Common Harmonics

    AFQevo ���� ���� ∗ 100 ���� Individual distortion rate (U % or I %): A ratio in % between the RMS value of the voltage ���� ���� or harmonic current (Un or In) and the RMS value of the fundamental component (U or I ����...
  • Page 39: 4�1�3�- Harmonic Compensation

    AFQevo 4�1�3�- HARMONIC COMPENSATION Active filters are devices responsible for the compensation of harmonic currents. Compensation is achieved by injecting harmonic currents equal to those in the installation in counter phase. This means that upstream of the filter connection point, the signal shows virtually no harmonic distortion ( Figure 31 AFQ-EVO CARGAS / LOADS RED / MAIN Figure 31:General connection diagram of an active filter.
  • Page 40: 4�3�- Nominal Current Dimensions

    Figure 32:Current in the load, in the filter and in the main. 4.3.- NOMINAL CURRENT DIMENSIONS The purchased active filter must be sized for the harmonic currents it has to filter. The nominal current of the AFQevo must be at least 20% higher than the maximum level of harmonics to be filtered. This factor may be higher depending on the installation features. The active filters can suffer from overloading when trying to cancel the harmonic currents in high-impedance, short-circuit mains. The clearest symptom for detecting such cases is that they originally start from a THD(V) (under voltage) of over 3%.
  • Page 41 AFQevo ���� = ���� − ���� �������� ���� ������������ ������������ �������������������� To calculate this safety factor you must first know the parameter called short-circuit ratio R at the connection point of the PCL transducers (not on the installation input). The short-circuit ∗ ������������(����) ] ���� ( ���������������� ) = [ ��������...
  • Page 42: 4�4�- Resonance Detection

    In certain cases, there may be a load that provides less impedance than the main, in which case a resonance phenomenon will be produced with that load. The AFQevo has a detection system for resonance with loads, which automatically deactivates the harmonic that causes that resonance.
  • Page 43: 4�5�1�- Upper Area

    AFQevo The display is divided into three areas ( Figure 36 Upper area Central area Lower area Figure 36:The display is divided into three areas� 4�5�1�- UPPER AREA The following will be displayed on the upper area:  A short description of the status of the device.
  • Page 44: 4�5�3�- Lower Area

    AFQevo Table 19: Central area keys� Function Restarts the device after an alarm. Starts the active filter. Stops the active filter. STOP 4�5�3�- LOWER AREA Figure 38: Lower area� The lower area displays the navigation and configuration keys of the device. Table 20: Lower area keys� Function Provides access to the main screen of the device. Shifting to the left.
  • Page 45: 5�- Start

    AFQevo 5�- START-UP When the device has been powered, one of the screens in appears on the display. Figure 39 Screen of a “Single” device or “Master” Screen of a “Slave” device Figure 39: Home screen� Before starting the active filter, it is necessary to follow the steps below: 1�- Use the key to navigate to the configuration screen and implement the appropriate configuration according to the existing installation. (see...
  • Page 46: 6�- Display

    In the upper part of the screen, a message with the current status of the device is shown ( Table Table 21:Status messages Status messages Starting Description The AFQevo is starting up. Init Description The device is starting the systems. Waiting comms Description...
  • Page 47: 6�1�2� - Device Slave

    Calibrating the internal sensors. Configuration Description Configuring the device. Description Device is operating. Sync Description The AFQevo is synchronising with the main. Charging Bus DC Description Charging process of the internal bus prior to start-up. Stop Description Device stopped. Alarm An alarm has been generated.
  • Page 48: 6�2�- Thd

    AFQevo 6.2.- THD Note: This screen is not visible on the “slave” devices. By pressing the key from the main screen, the THD display screen is accessed. Figure 42: THD display� It shows:  The Voltage in each of the phases, L1, L2 and L3.
  • Page 49: 6.4.- Power And Cos ɸ Of Mains

    AFQevo It shows:  The Voltage in each of the phases, L1, L2 and L3.  The Current in the Main in each of the phases, L1, L2, L3 and Neutral.  The Current in the Load in each of the phases, L1, L2, L3 and Neutral.
  • Page 50: 6.5.- Power And Cos ɸ Of Load

    AFQevo 6.5.- POWER AND COS ɸ OF LOAD Note: This screen is not visible on the “slave” devices. shows the power and cos ɸ of the load. Figure 45 Figure 45: Display of the power and cos ɸ of the load. It shows:  The Active Power (P), Reactive Power (Q) and Apparent Power (S).
  • Page 51: 6�7�- Current Harmonics (Mains)

    AFQevo 6.7.- CURRENT HARMONICS (MAINS) Note: This screen is not visible on the “slave” devices. In this screen, , the odd harmonics of the Main, from 3 to 25, are shown for each of Figure 47 the phases. Figure 47: Display of the Mains harmonics�...
  • Page 52: 6�9�- Wave Shape Of Main Current

    AFQevo 6.9.- WAVE SHAPE OF MAIN CURRENT Note: This screen is not visible on the “slave” devices. In this screen, , the wave shape of the main current is shown for each of the phases. Figure 49 Figure 49: Wave shape of main current�...
  • Page 53: 6�11�- Mains Phasors

    AFQevo 6.11.- MAINS PHASORS Note: This screen is not visible on the “slave” devices. In this screen, , the main phasors are shown. Figure 51 Figure 51: Main phasors� Use the keys to navigate through the different display screens. 6.12.- LOAD PHASORS Note: This screen is not visible on the “slave”...
  • Page 54: 6�13�- Alarms

    Table 22:Alarm messages� Alarm messages Overcurrent L1/L2/L3 Description The AFQevo current is too high. Corrective This alarm may be associated with transients and noise in the power supply voltage. Check the action quality of the power supply voltage. If it continues, contact the Technical Assistance Service...
  • Page 55: 6�14�- Warnings

    AFQevo Table 22 (Cont�) : Alarm messages� Alarm messages High temp Inductor Description The temperature of the inductors is very high. Corrective Check that the fans are working. Clean or replace the fans if necessary. If it continues, contact action...
  • Page 56 AFQevo This screen, , shows the active warnings. shows the warnings that can ap- Figure 55 Table 23 pear on the device’s display. Figure 55: Warnings� Use the keys to navigate through the different display screens. Table 23: Warnings messages�...
  • Page 57 AFQevo Table 23 (Cont�) : Warnings messages� Alarm and event messages Min temperature Description Temperature below the minimum operating value Corrective Wait for the environmental conditions to meet the requirements. If the alarm continues, contact action the Technical Assistance Service...
  • Page 58: 6�15�- Temperature

    , the temperatures of the inductors and IGBTs of the device are shown. Figure 56 Figure 56: Temperature� Note: The temperature of the inductors and IGBTs can be high. The AFQevo is protected from these temperatures and they do not present any risk for the device. Use the keys to navigate through the different display screens.
  • Page 59: 6�17�- Device Information

    AFQevo 6.17.- DEVICE INFORMATION In this screen, , the serial number, HMI and DSP versions of the device are shown. Figure 58 Figure 58: Device information� The touch panel of the display is calibrated from factory, but depending on the installation con- ditions, it may be necessary to recalibrate it.
  • Page 60: 6�18�- Slave Device Status

    AFQevo 6.18.- SLAVE DEVICE STATUS Note: This screen is not visible on the “slave” devices. Note: This screen is only displayed if a system has been configured with devices in parallel. This screen, shows the status of each “slave” device. Figure 60, Figure 60: Slave device status screen (1)�...
  • Page 61: 7�- Configuration

    AFQevo 7�- CONFIGURATION shows the main configuration screen. Figure 62 Figure 62: Main configuration screen. By pressing the key, the setup menu is accessed in display mode, i.e., all param- eters of the device are shown but they cannot be modified. By pressing the key, the setup menu is accessed in edit mode, i.e., the parame- ters of the device can be modified. In this case, before entering the setup menu it is necessary...
  • Page 62: 7�1�- Language

    AFQevo 7.1.- LANGUAGE In this screen, , the language of the display is selected. Figure 64 Figure 64: Configuration screen: Language. ● Language, display language. Press the key to access the next configuration step Press the key to access the main screen of the device without saving the configuration values. 7.2.- DEVICE SPECIFICATIONS Note : This screen is informative, it can not be modified.
  • Page 63: 7�3�- Installed Devices

    Figure 66: Configuration screen: Installed units ● Type of device: Master / Single / Slave The type of device is the first parameter that must be selected, with the following possible op- tions:  Single: select this option if the AFQevo does not have filters connected in parallel.  Master: select this option if the filter is going to be used as the “master” of a group of devices in parallel.  Slave: select this option if the device is going to be used as the “slave” of a group of devices in parallel.
  • Page 64: 7�4�- Working Mode

    AFQevo 7.4.- WORKING MODE Note: This screen is not visible on the “slave” devices. In this screen, , the following parameters of the device's operating mode are config- Figure 66 ured: Figure 67: Configuration screen: Operation mode. ● Mode In this parameter, the control algorithm that the device will use for harmonic filtering is selected, the options are:  TEMP: Temporary Mode, Harmonic filtering based on the instantaneous neutralisa- tion of all harmonics.
  • Page 65 AFQevo The phase balancing option in AFQe-3Wx-xxxx works in unbalances produced by loads connected between phases in three-phase mains without neutral. The AFQe-3Wx-xxxx does not compensate unbalances produced by single-phase loads connected between phase and neutral. Priority Enable this option so that the device prioritises the functions in case of filter current saturation due to overload: With the function enabled, the current balancing between phases and the reactive current com- pensation is prioritised over the harmonic filtering.
  • Page 66: 7�5�- Harmonics Selection

    AFQevo 7.5.- HARMONICS SELECTION Note: This screen is not visible on the “slave” devices. Note: The screen that appears if you have selected the operating mode FREQ: Frequency mode (“7.4.- WORKING MODE”) The harmonics to be filtered are selected in this screen, Figure 67 Figure 68: Configuration screen: Harmonic selection.
  • Page 67: 7�7�- Transformer Configuration

    AFQevo ● Min current The minimum load current to start the active filter is configured with this parameter. The AFQe- vo will stop when the load current is below the entered value and will start when it is higher. Range of values: Minimum value: 0 A Maximum value: 5000 A ● Current limit This parameter allows the maximum power of the active filter to be limited. The value is config- ured as a percentage with respect to the device's nominal power.
  • Page 68 ● Position The location of the transformers is configured with this parameter, the options are:  LOAD: If the transformers are installed in the load area, downstream from the AFQe-  MAIN: If the transformers are installed in the main area, upstream from the AFQevo. ● Ratio The transformer ratio is configured with this parameter, i.e., the ratio between the transformer primary and secondary.
  • Page 69: 7�8�- Alarms

    AFQevo 7.8.- ALARMS Note: This screen is not visible on the “slave” devices. The following alarms are enabled or not in this screen, Figure 71 Figure 71: Configuration screen: Alarms. ● Resonance If the control algorithm was selected in the Frequency mode and this alarm is enabled, when the device detects a potential resonance on an harmonic, it disables said harmonic and gener- ates an alarm, but it continues filtering the rest of the harmonics.
  • Page 70: 7�9�- Ethernet Communications

    AFQevo 7.9.- ETHERNET COMMUNICATIONS The communication parameters are configured in this screen, Figure 72 Figure 72: Configuration screen: Communications. By activating the DHCP option , the device assigns the IP automatically. If this option is not activated, the parameters must be configured manually: ● IP Address, IP address.
  • Page 71: 7�11�- Date / Time

    AFQevo ● Modbus device, modbus address. Press the key to access the next configuration step Press the key to access the main screen of the device without saving the configuration values. 7.11.- DATE / TIME The time parameters are configured in this screen, Figure 74 Figure 74: Configuration screen: Date / Time ● Time. ● Date. ● Time zone. By activating the Internet time option, the device synchronises with the time of the Web server to which it is connected.
  • Page 72: 7�12�- Save Data

    AFQevo 7.12.- SAVE DATA The modified configuration values are saved in the final setup menu screen, Figure 75 Figure 75: Final setup menu screen� Press the key to save the modified data. Press the key to exit the setup menu. Instruction Manual...
  • Page 73: 8�- Rs-485 Communications

    AFQevo 8�- RS-485 COMMUNICATIONS AFQevo devices have an RS-485 serial communication output with the MODBUS RTU ® com- munications protocol. For an installation with devices in parallel, the RS-485 connection can be made on any device. 8.1.- CONNECTIONS The RS-485 cable must be wired with twisted pair cable with mesh shield (minimum 3 wires), with a maximum distance between the AFQevo and the master device of 1200 metres�...
  • Page 74: 8�2�- Protocol

    AFQevo 8.2.- PROTOCOL In the Modbus protocol, the AFQevo uses the RTU (Remote Terminal Unit) mode. The Modbus functions implemented in the device are as follows: Functions 03 and 04. Reading of n Words (2 bytes). 8�2�1�- EXAMPLE OF MODBUS QUERY...
  • Page 75 AFQevo Table 26:Modbus memory map: Measurements with Load (Table 2)� Parameter Current L1 Current L2 Current L3 Units Fundamental harmonic 3rd order harmonic 5th order harmonic 7th order harmonic 9th order harmonic 11th order harmonic 13th order harmonic 15th order harmonic...
  • Page 76 21st order harmonic phase 0.001 x radians 23rd order harmonic phase 0.001 x radians 25th order harmonic phase 0.001 x radians 8.2.2.3.- Other parameters of the AFQevo filter Table 31:Modbus memory map: Filter parameters (Table 1)� Parameter Address Units Temperature of IGBTs ºC with 1 decimal...
  • Page 77 Hi [10] + Low [11] serial no. DSP software version HMI software version For a system with devices in parallel, the parameter value is that of the device connected with RS-485. 8.2.2.4.- AFQevo filter messages Table 34:Modbus memory map: Filter messages (Table 1)� Parameter Address...
  • Page 78 Maximum charge current For a system with devices in parallel, the parameter value is that of the device connected with RS-485. Table 37:Modbus memory map: Filter messages (Table 4)� Parameter Address AFQevo status Status (Decimal value) Description Start-up 10, 20, 30...
  • Page 79 AFQevo Table 38:Modbus memory map: Filter messages (Table 5)� Parameter Address Harmonics status Description Status 0x0001 Harmonic 3 0x0002 Harmonic 5 0x0004 Harmonic 7 0x0008 Harmonic 9 0x0010 Harmonic 11 1: Harmonic filtering 0x0020 Harmonic 13 0: Harmonic disabled 0x0040 Harmonic 15...
  • Page 80: 9�- Ethernet Communications

    For an installation with devices in parallel, the Ethernet connection can be made on any device. 9.1.- CONNECTION The AFQevo has an ethernet port. This type of communication creates an intranet with IP communications. If the device that connects to this port is a computer, the network cable must be a crossover...
  • Page 81 AFQevo The language of the web site can be modified using the buttons that appear on the upper right part of the page. To modify the Configuration parameters, it is necessary to enter the User and Password in the Administrator section. There are two types of user: 1�- User with write access, admin: Table 39: Default username and password for a user with write access�...
  • Page 82: 10�- Maintenance

    Follow the safety instructions in the section before car- “SAFETY PRECAUTIONS” rying out any maintenance on the AFQevo filters. Failure to follow these instructions may result in injury or even death� Certain components in the device can reach high temperatures� Allow the device to cool down before performing any maintenance operations�...
  • Page 83 AFQevo The points to be inspected are: 1�- Set the AFQevo in STOP mode and open the main switch (OFF position). 2�- Wait 1 minute for the capacitors to discharge. 3�- Clean the ventilation grilles, removing the dust. 4�- If there is a lot of dirt, remove the upper and lower fan covers and clean, removing the dust from the fans and the heatsink.
  • Page 84: 10�2�- Cooling Fans

    The set of fans must be replaced if they have exceeded their useful life or show signs of dete- rioration. In such cases, Circutor will provide a spare part that consists of a set of fans so that the device can be repaired quickly and easily.
  • Page 85: 10�2�1�- 30 A Afqevo : Afqe-Xxx-030M

    10�2�1�- 30 A AFQevo : AFQe-xxx-030M To change the fan set: Figure 81: Location of the cooling fans� 1�- Put the AFQevo in STOP mode and open the main switch (OFF position). 2�- Wait 1 minute for the capacitors to discharge 3�- Loosen the 6 fixing screws of the fan grille (Phillips screwdriver).
  • Page 86 6 screws. Note: recommended torque: 1�5 Nm 6�- Power up and start the AFQevo. Check the correct operation of the fans. 7�- Check the correct operation of the fans. To do so, access the maintenance screen through the setup screen by pressing the key and entering the password used to access the maintenance screen (Maintenance pass- word: 8888).
  • Page 87: 10�2�2�- 100 A Afqevo Rack-Type: Afqe-Xxx-100R

    8�- Reset the maintenance meter of the fans by pressing the key. 10�2�2�- 100 A AFQevo RACK-TYPE: AFQe-xxx-100R To replace the fan assembly: 1�- Put the AFQevo in STOP mode and open the main switch (OFF position). 2�- Wait 1 minute for the capacitors to discharge 3�- Loosen the 6 fixing screws in the upper cover and remove the cover, Figure 85 Note: Torx 25 screws Figure 85: Loosen the 6 fixing screws and remove the back cover.
  • Page 88 AFQevo Guide with display Fans cables Figure 86: Position of the guide with the cables from the screen and fans� 5�- Loosen the 2 fixing screws in the ventilation nozzle and remove the nozzle, Figure 87 Note: 8 mm hex screws Figure 87: Remove the ventilation nozzle� 6�- Loosen the fan’s 2 fixing screws (3 mm allen screws) and tilt it forwards to remove the fan, gently pull the cable away from the fan Figure 88 Figure 88: Remove the fan�...
  • Page 89 Connect the fans’ cables to the connector. 9�- Install the device’s upper cover by tightening the 6 fixing screws. Note: Recommended tightening torque: 1�5 Nm 10�- Re-connect to the electrical network and start up the AFQevo. 11�- Check that the fans are working properly. To do this, go to the maintenance screen, via the configuration screen, by pressing the key and entering the password to log into the maintenance screen (Maintenance password : 8888).
  • Page 90: 10�2�3�- 100 A And 200 A Afqevo Cabinet-Type : Afqe-Xxx-100C And Afqe-Xxx-200C

    10�2�3�- 100 A AND 200 A AFQevo cabinet-type : AFQe-xxx-100C AND AFQe-xxx-200C To replace the fan assembly: 1�- Put the AFQevo in STOP mode and open the main switch (OFF position). 2�- Wait 1 minute for the capacitors to discharge 3�- Access the 100 A modules via the front panel.
  • Page 91: 11�- Technical Features

    AFQevo 11�- TECHNICAL FEATURES Mains voltage AFQe-3W AFQe-4W Rated voltage Un 230 ... 480 Vac ± 10% 230 ... 400 Vac ± 10% Frequency Fn 50 / 60 Hz ± 5% Maximum THD V 25 % Earthing system TN, TT Power: AFQe-xxx-030M Maximum consumption...
  • Page 92 AFQevo (cont.) Filter specifications Up to 100 devices of different calibres Parallel connection Connection of the transformers only in the Master device Protective component against short circuits (AFQe-xxx-100C and AFQe-xxx-200C) Fuse NH00 125A gG 120kA 500Vac I2t 136kA2/s RS-485 Communications...
  • Page 93 AFQevo Mechanical features: AFQe-xWS-030M Dimensions (mm) Figure 91 Weight 31 kg Enclosure Galvanised steel 1.5 mm Noise 65 dBA Connections Type Main M6 ring terminal 12 mm 2.2 ... 2.4 Nm Earth M6 ring terminal 16 mm 2.2 ... 2.4 Nm...
  • Page 94 AFQevo Mechanical features: AFQe-xWF-030M Dimensions (mm) Figure 92 Weight 31 kg Enclosure Galvanised steel 1.5 mm Noise 65 dBA Connections Type Earth M6 ring terminal 2.2 ... 2.4 Nm Hex 10 mm Connections Type Main End cap 5 mm 1.5 ... 1.8 Nm...
  • Page 95 AFQevo Mechanical features: AFQe-xxx-100R Dimensions (mm) Figure 93 Weight 70 kg Enclosure Galvanised steel 1.5 mm Noise < 65 dBA Connections Type Main M8 ring terminal 23 mm 8 ... 10 Nm Earth M6 ring terminal 10 ... 14 Nm...
  • Page 96 AFQevo Mechanical features: AFQe-xxx-100C Dimensions (mm) Figure 94 Weight 206 kg Enclosure Free-standing sheet steel cabinet, for installation indoors, without removable parts. Noise < 65 dBA Connections Type Neutral Ring terminal 12 mm 35 Nm Hex 13 mm Earth Ring terminal...
  • Page 97 AFQevo Mechanical features: AFQe-xxx-200C Dimensions (mm) Figure 95 Weight 276 kg Enclosure Free-standing sheet steel cabinet, for installation indoors, without removable parts. Noise < 65 dBA Connections Type Neutral Ring terminal 12 mm 35 Nm Hex 13 mm Earth Ring terminal...
  • Page 98: 12�- Technical Service

    • CIRCUTOR accepts no liability due to the possible damage to the unit or other parts of the installation, nor will it cover any possible sanctions derived from a pos- sible failure, improper installation or “improper usage” of the unit. Consequently,...
  • Page 99: 14�- Ce Certificate

    AFQevo 14�- CE CERTIFICATE Instruction Manual...
  • Page 100 AFQevo Instruction Manual...
  • Page 101 AFQevo Instruction Manual...
  • Page 102 CIRCUTOR, SA Vial Sant Jordi, s/n 08232 - Viladecavalls (Barcelona) Tel: (+34) 93 745 29 00 - Fax: (+34) 93 745 29 14 www.circutor.com central@circutor.com...