Limitless™ WGLA Series
SYMPTOM
Red LED is not ON and buzzer does
not sound when Limitless™ switch is
actuated (green LED ON, amber LED
OFF)
Buzzer not sounding when
Limitless™ switch is actuated (green
LED ON, amber LED OFF)
NPN output is not changing state
when Limitless™ switch is actuated
(green LED ON, amber LED OFF)
CAUSE
Limitless™ switch is not paired
to WPMM
External actuator of
Limitless™ switch damaged
Actuating head of Limitless™
switch damaged
Limitless™ switch internal
electronics damaged
Amber LED burnt out or
damaged electronics of
WPMM
Red LED burnt out
Limitless™ switch is not paired
to WPMM
External actuator of
Limitless™ switch damaged
Actuating head of Limitless™
switch damaged
Limitless™ switch internal
electronics damaged
Amber LED burnt out or
damaged electronics of
WPMM
Buzzer burnt out
Limitless™ switch is not paired
to WPMM
Incorrect connections
External actuator of
Limitless™ switch damaged
Actuating head of Limitless™
switch damaged
Limitless™ switch internal
electronics damaged
Damaged output
Issue 2
RESOLUTION
Pair Limitless™ switch to WPMM per Section 5.4
Replace Limitless™ actuator
Replace Limitless™ actuating head
Replace Limitless™ switch
Replace WPMM
Replace WPMM
Pair Limitless™ switch to WPMM per Section 5.3
Replace Limitless™ actuator
Replace Limitless™ actuating head
Replace Limitless™ switch
Replace WPMM
Replace WPMM
Pair Limitless™ switch to WPMM per Section 5.3
Check for correct connections to output terminal
"O" with respect to minus "-" terminal
Replace Limitless™ actuator
Replace Limitless™ actuating head
Replace Limitless™ switch
Replace WPMM