U2" Outdoor Unit; Instantaneous Failure - Daikin VRV III REYQ8PY1B Service Manual

R-410a heat recovery 50hz
Hide thumbs Also See for VRV III REYQ8PY1B:
Table of Contents

Advertisement

SiBE37-701
U2
3.46 "
" Outdoor Unit:

Instantaneous Failure

U2
Remote
Controller
Display
Applicable
REYQ8P~48P
Models
Method of
Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Malfunction
Detection
Malfunction
When the voltage aforementioned is not less than 780V or not more than 320V, or when the
current-limiting voltage does not reach 200V or more or exceeds 740V.
Decision
Conditions
Supposed
Causes
Troubleshooting
Power Supply Insufficient or
Power supply insufficient
Instantaneous power failure
Open phase
Defect of inverter PC board
Defect of outdoor control PC board
Main circuit wiring defect
Faulty compressor
Faulty fan motor
Faulty connection of signal cable
Troubleshooting by Indication on the Remote Controller
329