SiBE37-701
3.5.2 Pump-down Residual Operation in Heating Operation and
Simultaneous Cooling / Heating Operation
Actuator
Compressor 1
Compressor 2
Compressor 3
Outdoor unit fan 1
Outdoor unit fan 2
Electronic expansion valve (Main) EVM
Electronic expansion valve
(Supercooling)
Electronic expansion valve
(Refrigerant charge)
Four way valve (Heat exchanger
switch)
Four way valve (High/low pressure
gas pipe switch)
Solenoid valve (Main bypass)
Solenoid valve (Hot gas)
Solenoid valve (Refrigerant
regulator liquid pipe )
Solenoid valve (Refrigerant
regulator gas vent pipe)
Solenoid valve (Refrigerant
regulator exhaust pipe)
Solenoid valve (Refrigerant
regulator discharge pipe)
Ending conditions
* Pe_min and Pc_max indicate the minimum and maximum values in the system, respectively.
Function
Elect.
symbol
Symbol
REYQ
REMQ
M1C M1C
M2C M2C
124 Hz+OFF+OFF
M3C M3C
M1F
M1F
Fan control
M2F
M2F
Y1E
When 20SA=ON: 0 pls
Y1E
Y3E
When 20SA=OFF: 1375 pls
Y2E
EVT
Y3E
0 pls
Y5E
EVJ
Y4E
Y2E
80 pls
When outdoor heat exchanger
Y2S
is evaporator: ON
20SA
Y3S
Y9S
When outdoor heat exchanger
is condenser: OFF
20SB
Y8S
Y2S
OFF
Y5S
SVE
Y6S
OFF
Y10S
SVP
Y4S
Y5S
OFF
SVL
Y3S
Y4S
OFF
SVG
Y1S
Y1S
OFF
SVO
Y7S
Y7S
OFF
SVT
Y6S
Y8S
OFF
or
Master unit operation
• 3 min.
• Pe_min<0.25 MPa ∗
• Pc_max<3.13 MPa ∗
• Master unit Tdi>110°C
• Master unit Tp>140°C
Special Control
Slave unit operation
OFF
Fan control
When 20SA=ON: 0 pls
When 20SA=OFF: 1375 pls
0 pls
80 pls
When outdoor heat exchanger
is evaporator: ON
When outdoor heat exchanger
is condenser: OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF