Installing the equipment

2.2.1
Mounting
14
Fire & Security Products
Siemens Building Technologies Group
Equipment must be solidly mounted.
When detectors are inserted, detector bases are subject to pushing, pulling and shearing
stress and must be mounted accordingly. There must be at least 50cm free space be-
neath the detector for test purposes.
Detector bases must lie flat on the ceiling (do not mount on bumps or hollows, concrete
ridges etc.).
Fig. 10 Detector base mounted on concrete ridge
= distorted detector base = system fault
Fire detectors must be easily accessible for regular servicing.
The response indicator in the base must be easily visible from the alarm investigation
route.
Response indicator
Fig. 11 Response indicator clearly visible
See product packing sheets, for further details.
Concrete ridge
e1453b
12.2001