Download Print this page

Technical Data - Siemens 7XV5654-0BA00 Directions For Use Manual

Sync-transceiver optical- / electrical converter for time synchronization system for siprotec 4
Hide thumbs Also See for 7XV5654-0BA00:

Advertisement

Available languages

Available languages

English

Technical Data

Specification
Mechanical design
Housing
Dimensions
Weight
Degree of protection
Housing
Terminals
Auxiliary voltage U
H
Rated input voltage
- DC voltage
- AC voltage
Class of protection
Power consumption
- DC voltage
- AC voltage
Alarm relay output
Terminals
Test voltage
Switching voltage (nominal value)
Switching capability
Switching current
Fault indicator
Outputs at 9 Pin SUB-D socket X1
Connection
Electrical outputs
Cable length
Nominal output voltage
Nominal output current
Max. output current
62 / 69
Plastic EG90
see dimensional drawings
approx. 250g
according EN60529
IP 51 plastic
IP 20
24 V - 250 V DC ± 20 %
60 V - 230 V AC ± 20 % / 45-65 Hz
II / III
With Nominal voltage (typical value)
24-250V DC
230 V AC 50 Hz
115 V AC 60 Hz
Maximum approx. 15 VA
MSR-Relay, 1 NC (open) contact,
potential free
2-pol. Phoenix terminal
3,7 kV
eff
250 V DC
20 W/VA
1 A permanent
LED green: Internal 5 V voltage is o.k.
9-pol. Sub-D socket
2 electrical 24 V output at PIN 1/3 and PIN 4/8
maximum 10 m for electrical outputs
24V DC -20% +10%
55 mA
per output (only one output
used at a time)
100mA
if both outputs used in parallel
7XV5654-0BA00
typ. 6 VA
typ. 12 VA
typ. 7 VA
C53000-B1175-C168-1