Both electrical outputs at X1 fed from one input
Both output channels at X1 (At PIN 1/3 and PIN 4/8) can be fed from one input (R1 or
R2 / BI2) by switching at DIP switch S1 switch 3 to ´ON´. The input signal is seen
parallel on both outputs. If at DIP-switch S1 switch 4 in set to ´ON´ the electronic output
contact is active in addition.
Remark: When the output channels at X1 are switched together to one input, only one
input can by used. No input signals on both inputs are allowed then.

Function

General description
The housed signal converter is a hard-wired and tested functional unit. It is provided
with a snap-on mounting device for a 35 mm DIN EN 50022 rail and with screw-type
terminals for safe connection of the auxiliary power supply. At it's screw terminals the
power supply, an alarm contact, the binary input and the electronic relay output can be
connected. The two 24 V outputs are connected at a 9 pin Sub-D socket. The two fiber-
optic inputs are attached with ST-connectors. The unit is free of silicone and halogen as
well as flame-retardant.
Hardware-Structure
R1
P5
RCV1
P24
X1/
1
Electrical output
Fig. 9: Hardware-Structure
52 / 69
Optical input
R2
S1/1
S1/2
S1/3
GND
GND
RCV2
8
3
4
Binary input
X5/
1
2
3
1
X100
2
P5
P5
K2
S1/4
X6/
1
Electronic relay
7XV5654-0BA00
Auxilliary voltage
X2/
N/L-
L1/L+
P5
GND
P24
&
GND
2
X7/
1
2
Alarm relay