Download Print this page

Siemens 7XV5654-0BA00 Directions For Use Manual page 65

Sync-transceiver optical- / electrical converter for time synchronization system for siprotec 4
Hide thumbs Also See for 7XV5654-0BA00:

Advertisement

Available languages

Available languages

7XV5654-0BA00
Interference immunity
IEC 255-22 (product standards)
EN 61010-1 (Generic standard)
High frequency test
IEC 60255-22-1, class III
VDE 0435 part 303, class III
Electrostatic discharge (ESD)
IEC 61000-4-2, class III
IEC 60255-22-2 class III
EN 61000-4-2, of degree 4
Irradiation with HF field, non modulated
IEC 60255-22-3, Klasse III
Irradiation with HF field, amplitude modulated
IEC 61000-4-3
ENV 50140, class III
EN 61000-4-3
Irradiation with HF field, pulse modulated
IEC 61000-4-3
ENV 50140 / ENV50204, class III
Fast transient disturbance / burst
IEC 61000-4-4, class IV
IEC 60255-22-4, class IV
EN 61000-4-4, class IV
Fast transient disturbance / burst
IEC 61000-4-4, class III
IEC 60255-22-4, class III
EN 61000-4-4, class III
Line contucted HF, amplitude modulated
ENV50141, class III
Immunity to power frequency magnetic field
EN 61000-4-8, class IV
C53000-B1175-C168-1
1 MHz; 400 surges per s; duration 2 s
2,5 kV long. voltage;
1,0 kV transverse voltage
4 kV contact discharge,
8 kV air discharge,
both polarities; 150 pF; Ri = 330 Ohm
10 V/m; 27 MHz to 500 MHz
10 V/m; 80 MHz to 1000 MHz;
80% AM; 1kHz
10 V/m; 900 MHz;
repetition frequency 200 Hz;
duty cycle of 50% or duty cycle of 100%
On auxiliary voltage inputs
4 kV; 5/50 ns; 5 kHz;
burst duration 15 ms
Repetition 300 ms; both polarities;
Ri = 50 Ohm; Test duration 1 min
On signal lines
2 kV; 5/50 ns; 5 kHz;
burst duration 15 ms
Repetition 300 ms; both polarities;
Ri = 50 Ohm; Test duration 1 min
10 V; 150 kHz bis 80 MHz;
80% AM; 1 kHz
30 A/m, durable ; 300 A/m for 3s;
50 Hz