Configuration; Configuration Checklist; Configuring Ip Settings Via The Nk823X Web Server - Siemens NK8237 MP4.70 Installation Function & Configuration Commissioning Safety Regulations

Firewall application for sinteso stt20 and cerberus pro fire detection systems
Table of Contents

Advertisement

Configuration

6

Configuration checklist

6 Configuration
6.1
6.2
30
Building Technologies
Fire Safety & Security Products
Configuration checklist
Verify that you have satisfied the items needed in the first checklist before
proceeding to the configuration checklist that follows.
The following abbreviations are used in the checklists:
DMS8000 Network Connectivity Guide
DMS-CG:
A6V10359485)
DMS-ICC: Product-specific (e.g. MM8000)
Commissioning Guide
Items needed for configuration
FS20/STT20/FS720 system commissioned.
Danger Management software installed (at least Composer - see DMS-ICC).
NK8237 unit(s) must be installed.
The network configuration must be defined, including all IP addresses, IP
masks and the default gateway. If multiple routing is required, each route
should be defined, including the destination IP address, mask, and gateway.
Ports to be enabled according to the specific firewall application.
Configuration workflow
1. To allow the NK8237 to communicate on the network, configure the NK8237 IP
address(es) via the NK823x Web Server [➙ 30] or the NW8202 [➙ 31].
2. In Composer, create [➙ 33] NK8237 firewall project by restoring the default
predefined firewall project.
3.
Configure [➙ 34] the NK8237 Ethernet connections (TCP/IP and BACnet/IP).
4.
Configure [➙ 35] the firewall.
(optional)
5.
Configure [➙ 38] the routing table.
6.
Download [➙ 42] the configuration to the NK8237 via Composer.
Testing and commissioning tasks
1.
Test the configuration.
2.
Troubleshoot [➙ 45] and maintain the system using the NW8204 Tool.

Configuring IP settings via the NK823x Web Server

This configuration must be performed before the NK8237 can be configured at the
client's site. This procedure details how to send the IP configuration information;
that is, the IP address, Subnet mask, and Default address to the NK8237 via the
NK823x Web Server.
Note: This configuration procedure can be performed prior to shipping the
NK8237 to the client, or at a later time at the client's site
1. Set the Service PC IP address to 192.168.9.x (for example 192.168.9.254, to
use the Ethernet port 1 with default IP address 192.168.9.41) or to
192.168.10.x (for example 192.168.10.254, to use the Ethernet port 2 with
default IP address 192.168.10.41) and the subnet mask to 255.255.255.0.
-
Make note of the current IP address before replacing it with the new one.
2. Remove the cover of the NK8237 to be configured.
(document no.
Installation, Configuration &
A6V10403182_a_en
30.09.2014