Download Print this page

Technical Data - ABB RDCO-04 Quick Start Manual

Ddcs communication option modules

Advertisement

Installation Procedure
1.
Access the optional module slots on the drive. Whenever
necessary, refer to the Hardware Manual of the drive for
instructions on removing any covers.
2.
Insert the module carefully into the slot marked with
"DDCS" (BCU control unit slot 4) on the control board
until the retaining clips lock the module into position.
3.
Fasten the screws included in the package. Note that
correct installation of the screws is essential for fulfilling
the EMC requirements and for proper operation of the
module.
4.
Lead the fiber optic cables from the external device to the
appropriate channel(s) of the RDCO. Inside the drive,
route the cables as shown in its Hardware Manual. Make
sure the cables are not kinked or laid against sharp
edges. Observe colour coding so that transmitters are
connected to receivers and vice versa. In case multiple
devices are to be connected to one channel, they must
be connected in a ring.

Technical data

Module types: RDCO-01(C), RDCO-02(C), RDCO-03(C),
RDCO-04(C)
Degree of protection: IP 20
Ambient conditions: The applicable ambient conditions
specified for the drive in its Hardware Manual are in effect.
www.abb.com/drives
www.abb.com/drivespartners
Connectors:
20-pin pinheader
4 transmitter/receiver connector pairs for fiber optic cable.
Type: Agilent Technologies Versatile Link. Communication
speed: 1, 2 or 4 Mbit/s
Operating voltage: +5 V DC ±10%, supplied by the control
unit of the drive.
Current consumption: 200 mA max.
Electromagnetic immunity: IEC 1000-4-2 (limits: industrial,
second environment); IEC 1000-4-3; IEC 1000-4-4;
IEC 1000-4-6
Electromagnetic emissions: EN 50081-2; CISPR 11
Dimensions (mm):
30
34
20

Advertisement

loading