TFP480
Page 6 of 10
DRY PIPE SYSTEM
ALARM
SPRINKLER
(IDC1)
TROUBLE
ALARM
SPARE
(IDC2)
TROUBLE
ALARM
SPARE
(IDC3)
TROUBLE
ALARM
SPARE
(IDC4)
TROUBLE
ALARM SILENCED
SUPERVISORY (SMP1)
SYSTEM TROUBLE
AC POWER
ACCEPT
SIGNAL
In Case of
Supervisory/
Trouble
Condition
Step 1. Verify that a fire condition does
not exist.
Step 2. Close the Main Control Valve
to prevent inadvertent water flow into
the system.
Step 3. Acknowledge the supervisory/
trouble notification by momentarily
pressing the ACCEPT SIGNAL KEY.
Doing so silences the tone-alert.
Step 4. Determine and correct cause
of supervisory/trouble notification, for
example:
• Loss of primary 120 VAC power
• Low battery condition
• High air pressure
• System or main control valve closure
Step 5. Reset the system as soon as
possible.
(SMP1)
TROUBLE
ALARM
SPARE
(SMP2)
TROUBLE
(NAC1) TROUBLE
SPARE (NAC2) TROUBLE
(RAC1) TROUBLE
SPARE (RAC2) TROUBLE
SYSTEM RELEASED
EARTH FAULT
SPARE
SPARE
SIGNAL
SYSTEM
SILENCE
RESET
OPERATOR INTERFACE CARD (FRONT SIDE)
DRY PIPE SYSTEM MODE
In Case of
Alarm
Condition
Step 1. Verify that a fire condition
exists and take appropriate action (that
is, evacuate the building and call fire
department).
Step 2. After the fire is extinguished,
reset the system.
If a fire condition does not exist and
prior to resetting the system, silence
the alarms as follows:
• First, momentarily press the ACCEPT
SIGNAL KEY a sufficient number of
times to stop the tone-alert.
• Second, momentarily press the SIG-
NAL SILENCE KEY.
Panel
Reference
IDC
NAC
LEDs
RAC
SPM
KEYS
FIGURE 3
Description
Initiating Device Circuit
(Low Air Pressure)
Notification Appliance Circuit
(Optional Notification Appliance)
Releasing Appliance Circuit
(Solenoid Valve)
Special Purpose Monitor
(Main Control Valve Closure,
System Control Valve Closure, or
High System Air Pressure)
System
Resetting
Step 1. Use the ACCEPT SIGNAL
KEY to accept every abnormal status
present in the system.
For example, when two red ALARM
and three yellow TROUBLE conditions
are present, the ACCEPT SIGNAL KEY
must be pressed five times. The Panel's
tone-alert turns off when all abnormal
conditions are accepted.
Step 2. Silence the alarms by pressing
the SIGNAL SILENCE KEY.
Step 3. Close the Main Control Valve.
Step 4. Place the Air Compressor Dis-
connect Switch to the OFF position.
Step 5. Open the Drain and Flow Test
Valves.
Step 6. Replace operated sprinklers.
Step 7. After the system drains com-
pletely, close the Drain and Flow Test
Valves.
Step 8. Place the Air Compressor Dis-
connect Switch to the ON position and
allow the system to automatically rees-
tablish its normal air pressure of 10 to
14 psi.
Need help?
Do you have a question about the RAPID RESPONSE RCP-1 and is the answer not in the manual?