Selection - Bosch Rexroth IndraDrive Project Planning Manual

Additional components
Hide thumbs Also See for Rexroth IndraDrive:
Table of Contents

Advertisement

Rexroth IndraDrive

Selection

460
i = 0.52
380
AC(200...240)V
DST**/*/240-460
0
200
220
DOK-INDRV*-ADDCOMP****-PR02-EN-P
Select an autotransformer suited to both the line voltage and the power
requirements of the system.
Proceed with the selection as follows:
Determine the rating group using the required rated line voltage range
in the diagram "Classification of the three-phase alternating current
autotransformers and then locate the transformer ratio "i".
Calculate the actual transformer output voltage using the rated line
voltage and the transformation ratio "i".
Check the drive data. The output voltage of the transformer has an
effect on the drive data.
Select a three-phase autotransformer corresponding to the required
connected load.
i = 1.08
AC(480...500)V
DST**/*/500-460
AC(480...580)V
DST**/*/580-460
240
480
500
520
Fig. 4-2:
Classification of three-phase autotransformers in rating groups
i = 1.26
AC(570...690)V
DST**/*/690-460
540
560
580
600
Input voltage in V of the transformer
Transformers
i = 1.50
620
640
660
680
Ap5087f1.fh7
4-3
700