Installation and removal instructions for Series NRX
undervoltage release, shunt trip, and overcurrent
trip switch in left accessory tray
Accessory
locking tab
Figure 11. Step 5 (RF frame shown)
Step 6e: Route the two secondary leads behind the first molded
tab, down under a second molded tab, and out the end of the
accessory tray.
Molded tab 1
Molded tab 2
Figure 12. Step 6 (NF frame shown)
Figure 13. Step 6 (RF frame shown)
Step 7e: If there is another UVR or ST to install in the other available
space of the left accessory tray, install it by repeating Step 4 and
Step 5.
Step 8e: Carefully route the secondary leads of the second installed
accessory by following the same routing path and using the same
molded tabs as the first installed accessory from Step 6.
ST
ST
Molded tab 1
ST
Molded tab 2
Instruction Leaflet IL01301008E
UVR
Figure 14. Step 8 (NF frame shown)
Figure 15. Step 8 (RF frame shown)
Step 9e: The left accessory tray should look as shown in Figure 15
with two accessories installed and secondary wires properly routed.
Step 10e: Place the left accessory tray with the installed UVR and/
or ST accessories back in its original position. Be careful not to bind
secondary wires or connector plugs.
UVR
ST
Figure 16. Step 10 (NF frame shown)
Effective June 2015
ST
UVR
ST
EATON www.eaton.com