Rules for the branching of a sub-stub from a loop
Only one sub-stub is permitted between two FDnet/C-NET devices.
One sub-stub is permitted at the start and end of the loop respectively,
between the connection terminals of the fire control panel and the first line
device.
If there is more than one stub between two FDnet/C-NET devices, a line
separator must be fitted between the stubs.
The following figures show the common variants of a modernized detector line on
which the FDnet/C-NET devices (T) are installed with integrated line separation
function. The outgoing stub lines A to D are connected to the FDCL221 line
separators via terminal blocks or micro terminals (X).
Figure 5: Housing FDCL221 line separator in intermediate distributors
1 Intermediate distributor
2 FDnet/C-NET loop
3 Line separator FDCL221
A Sub-stub A
B Sub-stub B
Planning
Accessories
C Sub-stub C
D Sub-stub D
T FDnet/C-NET device
X Terminal blocks or micro terminals