iDM EIB/KNX Technical Documentation Installation Instruction page 9

Navigator control 2.0
Table of Contents

Advertisement

D I E E N E R G I E F A M I L I E
NAVIGATOR - EIB/KNX communication
Version: 25.08.2017
Softwareversion Navigator control : since mod20.3-0
Object
Data
Access
type
1
9
RO
2
9
RO
3
7
RO
4
5
RW
5
7
RO
6
9
RO
7
9
RO
8
9
RO
9
9
RO
20
9
RO
*21
7
RW
30
9
RO
31
9
RO
32
9
RO
33
9
RO
34
9
RO
35
9
RO
36
9
RO
50
7
RO
60
7
RO
61
7
RO
(C) IDM ENERGIESYSTEME GMBH
Designation
External temperature (B31)
Averaged external temperature
Current error code
System operating mode
Smart Grid Status
0 ... Utility lock and no PV current
1 ... Current from utility provider and no PV current
2 ... No current from utility provider and PV current
4 ... Utility lock and PV current
Heat accumulator (B38)
Cold reservoir (B40)
DHW sensor bottom (B41)
DHW sensor top (B48)
Fresh water temperature (B42)
Desired hot water temperature
Heat pump flow temperature (B33)
Heat pump return temperature (B34)
HGL Flow temperature (B35)
Heat source inlet temperature (B43)
Heat source outlet temperature (B36)
Air inlet sensor (B37)
Evaporater (heat exchanger) sensor (B72)
Heat pump operating mode
Status compressor 1
Status compressor 2
Technical manaul EIB/KNX
Navigator
Min.
Max.
parameter
value
value
SYSMODE
-1
5
-1 ... Off
0 ... Standby
1 ... Automatic
2 ... Absent
3 ... Holiday
4 ... Only hot water
5 ... Only heating
0
4
FW030
35
95
0
8
0 ... Off
1 ... Heating
2 ... Cooling
4 ... Priority
8 ... Defrosting
0
1
0 ... Off
1 ... On
0
1
Programmierung
Default-
Unit
value
[°C]
[°C]
1
[°C]
[°C]
[°C]
[°C]
[°C]
46
[°C]
[°C]
[°C]
[°C]
[°C]
[°C]
[°C]
[°C]
9

Hide quick links: