LG Hydro Kit ARNH10GK2A4 Installation Manual page 33

Air-to-water heat pump
Table of Contents

Advertisement

General Information
supports following thermostats.
Hydro Kit
Type
Mechanical
(1)
Electrical
(2)
(1) There is no electric circuit inside the thermostat and electric power supply to the thermostat is not
required.
(2) Electric circuit such as display, LED, buzzer, etc is included in the thermostat and electric power
supply is required.
(3) Thermostat generates "Heating ON or Heating OFF" signal according to user"s heating target
temperature.
(4) Thermostat generates both "Heating ON or Heating OFF" and "Cooling ON or Cooling OFF" signal
according to user"s heating and cooling target temperature.
CAUTION:
Choosing Heating / Cooling Thermostat
• Heating / Cooling Thermostat must have "Mode Selection" feature to distinguish operation
mode.
• Heating / Cooling Thermostat must be able to assign heating target temperature and cooling
target temperature differently.
• If above conditions are not kept, the unit can not operation properly.
• Heating / Cooling Thermostat must send cooling or heating signal immediately when
temperature condition is satisfied. No delay time while sending cooling or heating signal is
permitted.
Power
Operating Mode
Heating Only (3)
1~ 230 V
Heating / Cooling (4)
Heating Only (3)
1~ 24 V
Heating / Cooling (4)
Heating Only (3)
1~ 230 V
Heating / Cooling (4)
Heating Only (3)
1~ 24 V
Heating / Cooling (4)
Accessories Installation
Supported
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Hydro Kit Installation Manual 33

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hydro kit arnh04gk2a4

Table of Contents