General Technical Data - VARISCO JE Series Instructions For The Use And Maintenance

Hide thumbs Also See for JE Series:
Table of Contents

Advertisement

1
1
.
.
2
2
G
G
E
E
N
N
E
E
R
R
A
A
L
L
T
T
E
E
Below are the technical data and specifications common to all the different types of electrical
equipment supplied:
EXTERNAL CONFIGURATION OF THE
EQUIPMENT
CONDITIONS OF INSTALLATION
VENTILATION
TYPE OF CURRENT
POWER SUPPLY SYSTEM
INSULATION RATED VOLTAGE
AUXILIARY CIRCUITS RATED VOLTAGE
INPUT VOLTAGE RANGE OF VARIATION
RATED FREQUENCY RANGE OF VARIATION
IDENTIFICATION OF THE PROTECTIVE
EARTH CONDUCTOR
DEGREE OF PROTECTION
DEGREE OF PROTECTION WITH THE DOOR
OPEN
MEASURES FOR PROTECTION OF PERSONS
AGAINST ELECTRIC SHOCK
OPERATING TEMPERATURE
ATMOSPHERIC CONDITIONS CONSIDERED
POLLUTION DEGREE
INTENDED ALTITUDE OF THE PLACE OF
INSTALLATION
EARTHING SYSTEM TO WHICH THE
EQUIPMENT IS INTENDED TO BE
CONNECTED
TYPES OF ELECTRICAL CONNECTIONS OF
THE FUNCTIONAL UNITS
EMC ENVIRONMENT
1
Pollution degree 1 No pollution or only dry and non-conductive pollution occurs.
Pollution degree 2 Only non-conductive pollution occurs. Occasionally, condensation can cause temporary conductivity.
Pollution degree 3 Conductive pollution or dry non-conductive pollution that becomes conductive due to condensation.
Pollution degree 4 The pollution generates persistent conductivity caused by conductive dust, rain or snow.
2
The types of electrical connections of the functional units inside the equipment are indicated by a 3-letter code: the first letter indicates
the type of electrical connection of the main incoming circuit; the second letter indicates the type of electrical connection of the main
outgoing circuit and the third letter indicates the type of electrical connection of the auxiliary circuits. The three letters have the
following meanings:
F refer to fixed connections (the connection is connected or disconnected by means of a tool);
D refers to disconnected connections (the connection is connected or disconnected by intervening manually without using a
tool);
W refers to removable connections (the connection is connected or disconnected by setting the functional unit to service or
disconnected mode).
3
B Environment Low voltage public network for residential, commercial and light industrial systems.
A Environment Low voltage non-public network or industrial systems, including sources of high interference.
4/24
USE AND MAINTENANCE MANUAL - ELECTRICAL EQUIPMENT
C
C
H
H
N
N
I
I
C
C
A
A
L
L
D
D
A
A
T
T
A
A
1
2
3
CABINET
FIXED EQUIPMENT
NATURAL
ALTERNATE
THREE-PHASE (3F+PE)
< 1000 V
N/A
NOMINAL VOLTAGE +/- 10%
RATED FREQUENCY +/- 2%
YELLOW-GREEN
IP55
IP20
INSULATION OF LIVE PARTS
PROTECTION BY BARRIERS OR
ENCLOSURES
USE OF PROTECTION CIRCUITS
+40 °C,
-5 °C
CLEAN AIR,
50% RELATIVE HUMIDITY
AT A MAX TEMPERATURE OF +40 °C WITH
NO CONDENSATION
POLLUTION DEGREE 3
INFERIOR TO 1000 m
TN SYSTEM
FFF
ENVIRONMENT A
Ed. 2010/09 - Rev. 00 - Cod. M08527

Hide quick links: