Description of operation
Control panel enclosure: check correct
functioning of the door lock
Control panel: verification of the earthing
system's efficiency and tightening of the
various connections
Control panel: inspection of the identification
plates
and
marking,
presence and updates of wiring diagrams and
documentation
Power
supply
conductors
verification of the integrity and efficiency; visual
inspection of the status of the end parts of the
wires and lines
Conductors and lines: verification of the
phase-phase insulation resistance and that
between the power circuit conductors and the
equipotential protection circuit (measured with
a suitable instrument)
Conductors and lines: verification of the
continuity of the equipotential protection circuit
(measured with a suitable instrument)
Conductors and lines: verification of the
tightening of the terminals, the connections of
the terminal block and the numbering /
identification of the conductors
ATTENTION
The operations described above must be performed according to the indicated schedules. Failure to comply with
the indications shall exempt the Manufacturer from all responsibility with regards to the Guarantee.
Verify that the safety devices function properly after any maintenance, repairs or changes are made.
Refer to the attached technical documentation (circuit diagrams) to check the calibration of the
components.
It is recommended to keep proof of the inspections carried out, thereby reporting the relative
information and results on a special register, including the date when the inspection is performed, the type
of inspection, the machine/system in question, the person performing the inspection and its result,
specifying the corrective action to be implemented.
18/24
USE AND MAINTENANCE MANUAL - ELECTRICAL EQUIPMENT
verification
of
the
and
lines:
NOTE
Machine status / precautions
Controls engaged
Isolation for maintenance
Isolation for maintenance
Reference CEI EN 60204-1
point 18.3.
Repeat
the
test
machine part and its relative
equipment
is
replaced
modified.
Reference CEI EN 60204-1
point 18.2.
Repeat
the
test
machine part and its relative
equipment
is
replaced
modified.
Isolation for maintenance
when
a
or
when
a
or
Ed. 2010/09 - Rev. 00 - Cod. M08527