SECTION 5: UV LAMP INSTALLATION
2. Loosen (not remove) the lamp Water Tight
Connector nut (3) to release tension on the lamp
cable allowing the cable to slide freely through the
adapter. This will allow the male-threaded body
(5) portion of the lamp Water Tight Connector to
be threaded into the white quartz sleeve retaining
nut without twisting the lamp cable (after lamp
installation).
3. With the UV lamp installed inside the quartz sleeve
and six inches exposed, attached the lamp cable's
stepped 4-Pin Connector on to the four pins of the
UV lamp.
4. With the lamp cable/lamp connection complete
gently slide the remainder of the lamp w/ cable
through the Quartz Sleeve Retaining Nut and into
the quartz sleeve. With the lamp now inside the
quartz sleeve, gently continue to push the lamp (w/
connected lamp cable) into the quartz sleeve until
it stops, then pull out 1/2" of the lamp cable. This
will position the lamp properly inside the quartz
sleeve avoiding heat damage to the Quartz Sleeve
Module Faceplate and Quartz Sleeve Module.
5. With the UV lamp in its correct position inside the
quartz sleeve, thread the water tight connector
into the Quartz Sleeve Retaining Nut.
BIOSHIELD
Commercial UV Sterilizer Installation and User's Guide
®
6. With the "black" Water Tight Connector threaded
into the Quartz Sleeve Retaining Nut, tighten the
Cable Adapter Nut (3) to create a watertight seal on
the lamp's cable. Take care not to bend or damage
the Water Tight Connector's "gasket prongs"
during this process.
7. The UV lamp is now properly installed.