Siemens SIMATIC HMI TP 170A Equipment Manual page 83

Table of Contents

Advertisement

Number
220004
Communication is terminated and no update
is executed because the cable is not
connected or is defect etc.
220005
Communication is running.
220006
The connection is established to the
specified PLC via the specified interface.
220007
The connection to the specified PLC at the
specified interface is disconnected.
220008
The PLC driver cannot access the specified
interface or open it. It is possible that another
application is using this interface or an
interface is used which is not available on
the target device.
There is no communication with the PLC.
230000
The value entered could not be accepted.
The entered value is rejected and the
previous value is specified again.
Either the value range has been exceeded or
impermissible characters were entered.
230002
Since the current password level is
inadequate or the password dialog box was
closed with ESC, the entry is rejected and
the previous value is specified again.
230003
Changeover to the specified screen is not
executed because the screen is not
available/configured. The current screen
remains selected.
3)
240000
Runtime is operating in Demo mode.
There is either no Stopcopy license or it is
defect.
3)
240001
Runtime is operating in Demo mode.
Too many tags are configured for the
installed version.
3)
240002
Runtime is operating with a time-limited
standby authorization.
240003
Authorization cannot be executed.
ProTool/Pro RT is running in Demo mode.
240004
Error during reading the standby
authorization.
ProTool/Pro RT is running in Demo mode.
TP 170A Equipment Manual
Release 12/99
CuuDuongThanCong.com
Effect/Cause
System Messages
Remedy
Check the connection.
Check that:
the cable is plugged in,
the PLC is OK,
the correct interface is used,
the configuration is OK (interface
parameters, protocol settings, PLC
address).
Reboot the system if the system message is
displayed continuously.
Terminate all the programs which access the
interface and reboot the computer.
Use another interface which is available in
the system.
Enter a permissible value.
Activate an adequate password level using
Login.
Configure the screen.
Check the selection function.
Load the license.
Load an adequate license / powerpack.
Restore the full authorization.
Restart ProTool/Pro RT or reinstall it.
Restart ProTool/Pro RT, install the
authorization or repair the authorization (see
Commissioning Instructions Software
Protection).