Number
20013
VBScript.dll is not correctly installed.
Therefore, no scripts can be executed.
20014
A value is returned by the script function
which is not written in any configured return
tag.
20015
Too many scripts have been triggered in
quick succession.
If more than 20 scripts are queued to be
processed, any subsequent scripts are
rejected.
In this case, the script indicated in the
message is not executed.
30010
The tag could not accept the function result,
e.g. in the case of exceeding the value
range.
30011
A function could not be executed because
the function was assigned an invalid value or
type in the parameter.
40010
The function could not be executed since the
parameters could not be converted to a
common tag type.
40011
The function could not be executed since the
parameters could not be converted to a
common tag type.
50000
The operating unit receives data faster than it
is capable of processing. Therefore, no
further data is received until the data
currently available has been processed.
Data exchange then resumes.
50001
Data exchange has been resumed.
60000
This message is generated by the function
"Display system messages". The text to be
displayed is transferred to the function as a
parameter.
60010
The file could not be copied in the direction
defined because one of the two files is
currently open or the source/target path is
not available.
It is possible that the Windows NT user has
no access rights to one of the two files.
60011
An attempt was made to copy a file to itself.
It is possible that the Windows NT user has
no access rights to one of the two files.
70010
The application could not be started because
it could not be found in the path specified or
insufficient memory space was available.
TP 170A Equipment Manual
Release 12/99
CuuDuongThanCong.com
Effect/Cause
System Messages
Remedy
Re-install ProTool/Pro RT.
Select the specified script in the
configuration.
Check whether the script name has been
assigned a value.
Check where the scripts are being triggered
from.
Extend the times, e.g. the polling time of the
tags, which trigger the scripts.
Check the tag type of the function parameter.
Check the parameter value and tag type of
the invalid parameter.
If a tag is used as a parameter, check its
value.
Check the parameter types in the
configuration.
Check the parameter types in the
configuration.
Restart the function or check the paths of the
source/target files.
Using Windows NT with NTFS: The user
executing ProTool/Pro RT must be granted
access rights for the files.
Check the path of the source/target file.
Using Windows NT with NTFS: The user
executing ProTool/Pro RT must be granted
access rights for the files.
Check whether the application exists in the
specified path or close other applications.