Toshiba RAV-SM560XT-E Service Manual page 10

Under ceiling / console type
Hide thumbs Also See for RAV-SM560XT-E:
Table of Contents

Advertisement

3-2. RAV-SM800XT-E / RAV-SM800AT-E
Outer diameter of refrigerant pipe
Gas side ∅A
Liquid side ∅B
9.5 mm
TS sensor
Accumulator
(1500cc)
Rotary compressor
(DA220A2F-20L)
Pressure
(MPa)
Pd
Standard
3.3
Cooling
Overload
3.7
Low load
1.0
Standard
3.3
Heating
Overload
3.1
Low load
2.0
* 4 poles are provided to this compressor.
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
15.9 mm
Pd
TD sensor
4-way valve
(STF-0213Z)
Muffler
∅25 x L210
∅25 x L160
Pipe surface temperature (°C)
Discharge
Suction
Ps
(TD)
(TS)
0.9
89
8
1.1
87
17
0.8
22
2
0.6
93
0
1.1
75
20
0.2
90
–26
Air heat exchanger
TC sensor
Refrigerant pipe
at liquid side
Outer dia. ∅B
Packed valve
Outer dia. ∅B
Strainer
TO sensor
Heat exchanger∅8
1 row 30 stages
FP1.3 flat fin
Indoor heat Outdoor heat
exchanger
exchanger
(TC)
(TE)
8
40
14
46
1
1
54
0
52
15
25
–25
– 8 –
Indoor unit
TCJ
sensor
Outdoor unit
Modulating (PMV)
(SKV-18D26)
TE
sensor
Capillary
∅3 x ∅2
x L530
Compressor
revolutions
Indoor
per second
fan
(rps)
*
64
HIGH
45
HIGH
24
LOW
70
HIGH
24
LOW
90
HIGH
Refrigerant pipe
at gas side
Outer dia. ∅A
Max
50m
Packed valve
Ps
Outer dia. ∅A
Strainer
R410A 1.5 kg
Cooling
Heating
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
Indoor
Outdoor
27/19
35/–
32/24
43/–
18/15.5
–5/–
20/–
7/6
30.–
24/18
0
–20/(70%)