Toshiba CARRIER RAV-SP180CT-UL Installation Manual page 27

Air conditioner (split type) indoor unit under ceiling type
Table of Contents

Advertisement

Under Ceiling Type
Remote control switch
monitoring function
This function is available to call the service monitor
mode from the remote control during a test run to
acquire temperatures of sensors of the remote control,
indoor unit, and outdoor unit.
1. Push
and
buttons simultaneously for at least
4 seconds to call the service monitor mode.
The service monitor indicator lights up and the
header indoor unit number is displayed first. CODE
No.
is also displayed.
2. Pushing TEMP.
number of sensor, etc. (CODE No.) to be monitored.
(See the following table.)
3. Pushing
(left side of the button), select an
indoor unit to be monitored. The sensor
temperatures of indoor units and their outdoor unit in
the control group are displayed.
4. Push
button to return to the normal display.
2
4
1
Indoor unit data
CODE No.
01
Room temperature (remote control)
02
Indoor unit intake air temperature (TA)
Indoor unit heat exchanger temperature
03
Indoor unit heat exchanger temperature
04
Indoor unit fan cumulative operating hours
F3
F8
Indoor unit discharge air temperature
buttons, select the
3
Data name
(TCJ)
(TC)
(x1 h)
– 26 –
Outdoor unit data
CODE No.
Outdoor unit heat exchanger temperature
60
61
Outside air temperature (TO)
62
Compressor discharge air temperature (TD)
63
Compressor intake air temperature (TS)
64
65
Heatsink temperature (THS)
6A
Operating current (x1/10)
Compressor cumulative operating hours
F1
Installation Manual
Data name
(TE)
(x100h)
EN
26-EN

Hide quick links: