Under Ceiling Type
Filter sign setting
According to the installation condition, the lighting time
of the filter sign (Notification of filter cleaning) can be
changed.
Follow to the basic operation procedure
1
2
3
4
(
• For the CODE No. in Procedure
• For the [SET DATA] in Procedure
data of filter sign lighting time from the following
table.
Setup data
0000
0001
0002
0003
0004
To secure better effect of
heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator, etc. to circulate heat air
near the ceiling.
Follow to the basic operation procedure
1
2
3
4
(
• For the CODE No. in Procedure
• For the SET DATA in Procedure
data of shift value of detection temperature to be set
up from the table below.
Setup data
0000
0001
0002
0003
0004
0005
0006
23-EN
5
6
).
3
, specify [01].
4
, select the setup
Filter sign lighting time
None
150H
2500H (Factory default)
5000H
10000H
5
6
).
3
, specify [06].
4
, select the setup
Detection temp shift value
No shift
+1.8 °F (+1 °C)
+3.6 °F (+2 °C)
(Factory default)
+5.4 °F (+3 °C)
+7.2 °F (+4 °C)
+9.0 °F (+5 °C)
+10.8 °F (+6 °C)

Group control

Group control for system of multiple units
One remote control can control maximum 8 indoor
units as a group.
▼ Group control in single system
Outdoor
Outdoor
unit
unit
Indoor
Indoor
unit
unit
Remote
control
Finish of address setup by
power-ON
• For wiring procedure and wiring method of the
individual line (Identical refrigerant line) system,
follow to "Electric work".
• Wiring between lines is performed in the following
procedure.
Connect the terminal block (A/B) of the indoor unit
connected with a remote control to the terminal
blocks (A/B) of the indoor units of other indoor units
by wiring the inter-unit wire of the remote control.
• When the power supply has been turned on, the
automatic address setup starts and "
which indicates that address is being set up flashes
on the display part. During setup of automatic
address, the remote control operation is not
accepted.
Required time up to the finish of automatic
addressing is approx. 5 minutes.
NOTE
In some cases, it is necessary to change the address
manually after setup of the automatic address
according to the system configuration of the group
control.
Procedure example 1
Manual address setup procedure
While the operation stops, change the setup.
(Be sure to stop the operation of the unit.)
– 23 –
Installation Manual
Outdoor
Outdoor
Outdoor
unit
unit
unit
Indoor
Indoor
Indoor
unit
unit
unit
(Max. 8 units)
" display