Earthing Of E-N Windings - ABB ZX0 Manual For Installation And Operation

Gas-insulated medium voltage switchgear
Hide thumbs Also See for ZX0:
Table of Contents

Advertisement

Earthing of e-n windings

If the e-n windings of the voltage transformers are damped with
a resistor, the windings connected in an open delta are to be
earthed at one point. The circuit can be earthed
- in the low voltage compartment (figure 2.3.5.2.3) or
- on the terminal block of a voltage transformer (figure
2.3.5.2.4).
Perform measurements to ascertain which earthing method ap-
plies to your system.
Fig. 2.3.5.2.3: Earthing of the circuit in the low voltage compartment
Do not earth here!
Without earthing screw on
terminal "dn"
Fig. 2.3.5.2.4: Earthing the circuit on the terminal board of a transformer
Do not earth here!
Without earthing screw on
terminal "dn"
Earth here!
With earthing screw on
terminal "dn"
30 | Manual ZX0 HB 600 en - Revision 05
dn
dn
-T15L1
da
da
-F
dn
dn
-T15L1
da
da
-F
dn
-T15L2
-T15L3
da
-R
dn
-T15L2
-T15L3
da
-R
Earthing in the low voltage
compartment