ABB ZX0 Manual For Installation And Operation page 8

Gas-insulated medium voltage switchgear
Hide thumbs Also See for ZX0:
Table of Contents

Advertisement

You have chosen a gas-insulated switchgear of series ZX0 in block
design. This switchgear from the ZX range is notable for the fol-
lowing features:
− SF
gas-insulated with hermetically sealed pressure
6
systems
− Rated voltages up to 24 kV
− Up to 1250 A and 25 kA
− Single busbar design
− Up to six panels grouped together in a block (one common
gas compartment)
− Stainless steel enclosures, fabricated from laser cut sheet
steel
− Modular structure
− Switchgear with a leakage rate of less than 0.1 % per year
− Integrated routine leakage testing of the panel blocks ex-
works
− Indoor installation and free-standing installation
− Wall installation
− Panel widths 400 mm and 600 mm
Do not use cleaning agent containing chlorine for cleaning the switchgear.
If you have technical questions, please contact our service staff
Power technology customer service
8 | Manual ZX0 HB 600 en - Revision 05
Please observe further documents in addition to this manual. The
documents relevant to your switchgear are part of the final docu-
mentation.
&
Installation checklist
&
Order documents
− Single line diagram
− Front view
− Construction data if compiled specifically
for this order
− Circuit diagrams
− Earthing diagram – switchgear earth
to station earth (not part of ABB supply)
&
Instruction manuals
− Use of SF
insulating gas
6
− Circuit-breaker VD4 X0
− Snap-action mechanism for
switch-disconnector
− Stored-energy spring mechanism for
switch-disconnector with fuse
− Material supplement
&
Operating instructions and directions for components,
e.g.
− Surge arresters
− Current and voltage transformers
− Current and voltage sensors
− Protection and control devices
− Capacitive indicators.
MC 600 E
HB 605 E
BA 440 E
BA 445 E
BA 446 E
BA 509 E
Call number +49 180 6222-007