Connecting the unit

Setting centralized individual control

f For centralized individual control, RMC address of each ERV must be set equally from the OnOff controller .
f
OnOff Controller
ERV interface module "0"
• If you turn on the switch no . 00 of the OnOff controller, ERV with RMC address 0 will be turned on and starts to
operate .
NotE
other Installation Specification

External Control

Use an external control to interlock control the ERV with external
device or external contact point . The picture displays the condition
that external controller and kitchen hood are connected
f Using external controller
f
- It connects both sides of EXT1 .
- If the external controller 1 is set to On position, ERV is
operated in the last used condition .
f Using Kitchen hood
f
- It connects both sides of HOOD .
- If you enter a kitchen hood, the supply air operates in Turbo
fan speed and exhaust air operates in low fan speed .

Connecting external load

f Connection is necessary to use humidifying unit or damper
f
with the ERV
f When external damper is installed, damper will be opened
f
when the ERV is On and damper will be closed when the ERV
is OFF .
f Electric current load should not exceed 2 a under the output
f
terminal . You must install extra contact point relay when
electric current load should exceed 2 a . (220V)
f To use an external load, you must set the installation option .
f
(Refer to installation option 2 of the ERV)
CN4
ERV
MaIn:0
RMC:0
ERV
MaIn:1
RMC:0
HOOD EXT1
ENGLISH-24
DRY COnTaCT
Kitchen hood
External control 1
DRY COnTaCT
Damper or
Humidification